Publication 1734-UM001D-EN-P - April 2008
146
Troubleshoot with the Indicators
1734-OB2EP Protected Output Module
1734-IV2, 1734-IV4, and 1734-IV8 Source Input Modules
Protected
Sourcing
Output
Module
Status
Network
Status
1734
OB2EP
NODE:
0
1
Module Status
Network Status
Status of Output 0
Status of Output 1
Indication
Probable Cause
Recommended Action
I/O Status
Off
All outputs are inactive.
None.
Yellow
One or more output is active and under control.
None.
Flashing red
Open circuit detected - no load (Off-state only).
Connect load or disable no load detection.
Solid red
Short circuit detected (On-state only).
Remove short or overloaded circuit.
24VDC
Source
Input
Module
Status
Network
Status
1734
IV2
NODE:
0
1
24VDC
Source
Input
Module
Status
Network
Status
1734
IV4
NODE:
0
1
2
3
41974
Module Status
Network Status
Status of Input 0
Status of Input 1
Status of Input 2
Status of Input 3
1734-IV2
1734-IV4
24VDC
Source
Input
Module
Status
Network
Status
1734
IV8
NODE:
0
1
2
3
4
5
6
7
Status of Input 0 and 4
Status of Input 1 and 5
Status of Input 2 and 6
Status of Input 3 and 7
1734-IV8
Module Status
Network Status
Содержание 1734-IA2
Страница 4: ...Publication 1734 UM001D EN P April 2008 4 Summary of Changes Notes ...
Страница 12: ...Publication 1734 UM001D EN P April 2008 12 Table of Contents Notes ...
Страница 77: ...Publication 1734 UM001D EN P April 2008 Install POINT I O Modules 77 ...
Страница 78: ...Publication 1734 UM001D EN P April 2008 78 Install POINT I O Modules ...
Страница 179: ...Publication 1734 UM001D EN P April 2008 Default Data Maps 177 Notes ...
Страница 180: ...Publication 1734 UM001D EN P April 2008 178 Default Data Maps ...
Страница 236: ...Publication 1734 UM001D EN P April 2008 234 Notes ...
Страница 241: ......