Calibrate Your Analog Modules
127
Calibrate the Analog
Current Output Module
To calibrate your output module, connect the module in a DeviceNet system
similar to that shown in the figure, and use this procedure.
.
1.
Double-click the icon to bring up the General parameter dialog.
IMPORTANT
Apply power to the power supply and module for at least 10
minutes before calibrating the module. This allows internal
temperatures to stabilize and reduces drift errors.
0
1
0
1
0
1
0
1
0
1
0
1
44032
Power Supply Voltage
DeviceNet Input
PDN OE2C
250
Ω
Current Meter
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5