Publication 1734-UM015A-EN-E - November 2009
36
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Online Configuration using
RSNetWorx for DeviceNet
To set up a DeviceNet network using RSNetWorx for DeviceNet when
connected to the network, do the following:
1.
If you have a DNT file that has been configured, open the file in
RSNetWorx for DeviceNet. To do this, go to the Online mode by
pressing <F10>. You can also click Network > Online, or click the
Online button
.
RSLinx will start. If the Online path is not set in Network > Properties,
the Browse for network dialog box will appear.
2.
Navigate to the DeviceNet network or DeviceNet subnet if configuring
the backplane.
The OK button will become available when you select a valid network.
RSNetWorx will automatically browse the network to discover all the
participants.
3.
If there are any module identity issues, correct them before continuing.
4.
Ensure that the configuration in the DNT file matches the
configuration in each node.
In this section, it is assumed that all the work was done in the Offline
mode and that the DNT file contains all the correct information.