First start-up 

Installation, use and maintenance manual – GAHP A 

29

5

Figure 4.9  

 Connection of Wilo Stratos Para variable flow pump

IP 

 Two-position pump power switch

Fuse

PM   Hot water pump (primary circuit)
Pump signal 0-10 V wire colours
brown connect to - terminal
white connect to + terminal
black isolate
blue isolate

PM

L

230 V 1N - 50 Hz

N

F

SCH

IP

Figure 4.10  

 Connection of the Wilo Stratos Para variable flow pump 
powered by the appliance

PM 

 Hot water pump (primary circuit)

MA 

 Appliance terminal block

Pump signal 0-10 V wire colours
brown connect to - terminal
white connect to + terminal
black isolate
blue isolate

5  

 FIRST  START-UP

 

First start-up entails checking/setting up the combus-

tion parameters and may exclusively be carried out by a 

Robur TAC. NEITHER the user NOR the installation tech-

nician is authorised to perform such operations, under 

penalty of voiding the warranty.

5.1 

 

 PRELIMINARY  CHECKS

5.1.1 

   Preliminary checks for first start-up

Upon completing installation, before contacting the TAC the in-

staller must check:

 

Water, electrical and gas systems suitable for the required 

capacities and equipped with all safety and control devices 

required by the regulations in force.

 

Absence of leaks in the water and gas systems.

 

Type of gas for which the appliance is designed (natural gas 

or LPG).

 

Supply gas pressure complying with the values of Table 

3.3 

p. 22, with max tolerance ±15%.

 

Correct operation of the flue exhaust duct.

 

Power supply mains complying with the appliance's rating 

plate data.

 

Appliance correctly installed, according to the manufacturer's 

provisions.

 

System installed in a workmanlike manner, according to na-

tional and local regulations.

5.1.2 

   Abnormal or hazardous installation situations

Should any abnormal or hazardous installation situations be 

found, the TAC shall not perform first start-up and the appliance 

shall not be commissioned.

These situations may be:

 

Appliance installed inside a room.

 

Failed compliance with minimum clearances.

 

Insufficient distance from combustible or flammable mate-

rials.

 

Conditions that do not warrant access and maintenance in 

safety.

 

Appliance switched on/off with the main switch, instead of 

the provided control device.

 

Appliance defects or faults caused during transport or instal-

lation.

 

Gas smell.

 

Non-compliant mains gas pressure.

 

Non-compliant flue gas exhaust.

 

All situations that may involve operation abnormalities or 

are potentially hazardous.

Содержание GAHP A indoor

Страница 1: ...GAHP A Installation use and maintenance manual powered by gas and renewable energies Air Water gas absorption heat pump...

Страница 2: ...tered trademarks contained within this publication are not affected With the aim of continuously improving the quality of its products Robur S p A reserves the right to modify the data and contents of...

Страница 3: ...pump p 20 3 5 Antifreeze function p 20 3 6 Antifreeze liquid p 21 3 7 System water quality p 21 3 8 System filling p 22 3 9 Fuel gas supply p 22 3 10 Combustion products exhaust p 23 3 11 Flue gas con...

Страница 4: ...r Box optional interface devices complementary to DDC which may be used to broaden its func tions heating cooling DHW production service demands and control of system components such as third party ge...

Страница 5: ...P unit uses the ammonia water absorption cycle The water ammonia solution is contained in the sealed circuit The solution is harmful for health if it is ingested inhaled or comes in contact with the s...

Страница 6: ...ed Furthermore they comply with the requirements of the follow ing standards EN 378 Refrigerating systems and heat pumps Other applicable provisions and standards The design installation operation and...

Страница 7: ...steel pipe and alumin ium fins Automatic microprocessor controlled finned coil defrosting valve Low power consumption refrigerant fluid oil pump Standard or S1 silenced fan reduction of electrical co...

Страница 8: ...Features and technical data 8 1 Figure 1 2 Dimensions standard fan Figure 1 3 Dimensions low consumption silenced fan...

Страница 9: ...t view 1 Fan 2 Tapping point for flue analisys 3 Gas valve 4 Combustion air intake 5 Combustion blower 6 Ignition transformer 7 Tmix air gas mixture temperature probe 8 Oil pump 9 Water inlet connecti...

Страница 10: ...ernal components left side view 1 Manual reset of the flue exhaust thermostat 2 Sensing element of the flue exhaust thermostat 3 80mm flue gas exhaust 4 Generator fin temperature sensor 5 Flame sensor...

Страница 11: ...nual GAHP A 11 1 Figure 1 6 Internal components right side view 1 TG generator temperature probe 2 Safety valve 3 Delivery pipe flowmeter 4 Flow temperature probe 5 Limit thermostat 6 Defrosting valve...

Страница 12: ...trodes FLS Flame sensor LS Gas valve ON indicator lamp GV Gas solenoid valve TC Manual flue gas thermostat TL Generator limit thermostat FM Flowmeter CWS Condensate water sensor VD Defrosting valve FA...

Страница 13: ...rature probe TMIX Combustion air temperature sensor TA Ambient air temperature sensor TG Generator temperature sensor TF Fumes temperature sensor or generator fin sensor TEVA Evaporator outlet tempera...

Страница 14: ...10 board connector on Mod10 JP10 6 pole flame controller connector JP12 Flue gas probe or generator fin probe input JTAG S61 board programming connector MAIN 230V L N S61 board supply input 230 Vac N...

Страница 15: ...HPMP Primary circuit hot water pump control output 0 10 V CPMP S1 low consumption fan control output 0 10 V NC1 C1 Status indication of locking warnig error CN5 Blower control J82 W10 auxiliary contr...

Страница 16: ...lso be controlled via generic request de vices e g thermostat timer switch contactor fitted with voltage free NO contact This system only provides elementary control on off with fixed set point temper...

Страница 17: ...4 0 maximum flow rate of flue gas condensate l h 4 0 water content inside the appliance l 4 Water fitting type F thread 1 1 4 Gas connection type F thread 3 4 Flue gas exhaust diameter mm 80 residual...

Страница 18: ...able for the load Do not stand under suspended loads 2 2 HANDLING 2 2 1 Handling and lifting Always handle the appliance in its packing as delivered by the factory To lift the appliance use straps or...

Страница 19: ...ble mate rials or components in compliance with applicable regulations 2 4 2 Clearances around the appliance The minimum clearance distances shown in Figure 2 2 p 19 bar any stricter regulations are r...

Страница 20: ...2 isolation ball valves on the inlet water piping 1 separator filter 1 flow regulation valve if the circulation pump is with constant flow 1 water circulation pump towards the appliance on the output...

Страница 21: ...GA Glycol Water glycol mixture freezing temper ature Percentage of increase in pressure drops Loss of efficiency of unit 10 3 C 15 5 C 6 0 0 5 20 8 C 8 0 1 0 25 12 C 10 0 2 0 30 15 C 12 0 2 5 35 20 C...

Страница 22: ...ient gas pressure for the appliance 3 9 4 Supply gas pressure This appliance is equipped for a maximum gas supply pressure of 50 mbar The appliance s gas supply pressure both static and dynamic must c...

Страница 23: ...ed firm with materials and components complying with the regulations in force in the country of installation Always provide a socket for flue gas analysis in an accessible position In case the check v...

Страница 24: ...ions in force It is forbidden to use gas pipes as earthing Cable segregation Keep power cables physically separate from signal ones Do not use the power supply switch to turn the ap pliance on off Nev...

Страница 25: ...electrical board of the appliance according to the Procedure 4 2 p 24 2 Connect the three lead in wires to the terminal block TER in the electrical panel on the machine 3 Provide the earth lead in wir...

Страница 26: ...cable section only or OPEN Detail B if the node is intermediate two connected CAN bus cable sections 4 Connect the DDC or the CCP CCI to the CAN bus cable ac cording to the instructions in the follow...

Страница 27: ...ND JUMPER J1 P8 L H GND H L JUMPER J21 P8 H L GND C D E Place the CLOSED J21 Jumpers Detail A if the node is terminal one connected CAN bus cable section only or OPEN Detail B if the node is intermedi...

Страница 28: ...terminal block L Phase N Neutral Components NOT SUPPLIED PM Water pump 700 W Note 1 Jumper J10 must be closed if the installed pump is not a Wilo electronic pump Jumper J10 must be opened if the insta...

Страница 29: ...and equipped with all safety and control devices required by the regulations in force Absence of leaks in the water and gas systems Type of gas for which the appliance is designed natural gas or LPG...

Страница 30: ...ons reset errors Paragraph 7 5 p 33 Menu 3 display and setting to set the value of some sys tem parameters e g water setpoint temperature the val ues are initialised by the TAC at first start up It is...

Страница 31: ...x settings Specific technical and system knowledge is required for complex settings Contact a TAC 6 NORMAL OPERATION This section is for the end user The use of the device by the end user is only per...

Страница 32: ...system manager Environmental or operational heavy conditions In environmental or operational conditions particularly heavy for example heavy duty use of the appliance salty environment etc maintenance...

Страница 33: ...ntact the TAC 7 5 2 Locked out appliance An external intervention reset or repair is required due to an appliance fault or problem with the system A reset may be enough for a temporary and provisional...

Страница 34: ...er 21 If the code persists shows up again or in case of doubt contact the TAC 408 Flame controller error NA Contact authorised Technical Assistance 410 Low hot water flow Reset is automatic when the t...

Страница 35: ...automatically 20 minutes after the code is generated Reset may be performed from the DDC CCI or from the S61 board menu 2 parameter 21 If the code persists shows up again or in case of doubt contact...

Страница 36: ...the TAC 482 Invalid bank 2 parameters Reset is automatic when the triggering condi tion ceases Contact the TAC 484 Transformer or 24 Vac fuse fault NA Contact the TAC 485 Invalid module type configura...

Страница 37: ...TO 0 021 kW Standby mode P SB 0 005 kW Crankcase heater mode P CK kW Other items Capacity control For air to water heat pumps Rated air flow rate outdoors __ 11000 m h Sound power level indoors outdoo...

Страница 38: ...W Crankcase heater mode P CK kW Other items Capacity control For air to water heat pumps Rated air flow rate outdoors __ 11000 m h Sound power level indoors outdoors L WA 74 dB For water or brine to w...

Страница 39: ......

Страница 40: ...111 F 39 035 884165 www robur it robur robur it 26 04 2021 21MCLSDC015 Code D LBR548 Revision AA Robur is dedicated to dynamic progression in research development and promotion of safe environmentally...

Отзывы: