background image

Installation and user manual 

 

 

 

 

 

 

Contents 

 

Contents ............................................................................................................................................................ 2

 

1

 

Introduction ............................................................................................................................................... 3

 

1.1

 

Introduction and referenced European laws .................................................................................... 3

 

1.2

 

Warnings .......................................................................................................................................... 3

 

2

 

Technical features ..................................................................................................................................... 4

 

2.1

 

Dimensions ....................................................................................................................................... 4

 

2.2

 

Main advantages .............................................................................................................................. 4

 

2.3

 

Construction details .......................................................................................................................... 5

 

3

 

Installer instruction .................................................................................................................................... 6

 

3.1

 

Packing and product identification ................................................................................................... 6

 

3.2

 

Mounting ........................................................................................................................................... 7

 

3.2.1

 

Installation room ........................................................................................................................... 7

 

3.2.2

 

Wall mounting .............................................................................................................................. 7

 

3.3

 

System cleaning ............................................................................................................................... 8

 

3.4

 

Gas system ...................................................................................................................................... 8

 

3.5

 

Flue gas system ............................................................................................................................... 8

 

3.5.1

 

Pipe maximum length .................................................................................................................. 8

 

3.5.2

 

Installation of one single thermal assembly with flue gas exhaust pipe running inside a cavity 

for pipe routing (open chamber operation) ............................................................................................... 8

 

3.5.3

 

Connection to a flue gas manifold ............................................................................................... 9

 

3.6

 

Condensate discharge ................................................................................................................... 10

 

3.6.1

 

Siphon along the discharge piping ............................................................................................. 11

 

3.7

 

Hydraulic connection ...................................................................................................................... 11

 

3.7.1

 

Operating pressure .................................................................................................................... 12

 

3.7.2

 

Filling and emptying ................................................................................................................... 12

 

4

 

Installation drawings ............................................................................................................................... 12

 

5

 

Power supply system .............................................................................................................................. 15

 

5.1

 

Power supply .................................................................................................................................. 15

 

5.2

 

Warnings ........................................................................................................................................ 16

 

5.3

 

Electrical connections ..................................................................................................................... 16

 

5.3.1

 

5.3.1 Connection to temperature regulation devices ................................................................. 16

 

5.3.2

 

Antifreeze protection .................................................................................................................. 16

 

5.3.3

 

Pump connection ....................................................................................................................... 16

 

5.3.4

 

Room Thermostat connection (on/off)) ...................................................................................... 18

 

5.3.5

 

External probe connection ......................................................................................................... 18

 

5.3.6

 

Connection of an external regulation 0-10v ............................................................................... 18

 

5.3.7

 

Connection of an alarm device .................................................................................................. 18

 

5.3.8

 

Connection of a remote control .................................................................................................. 18

 

5.3.9

 

Emergency mode ....................................................................................................................... 18

 

5.3.10

 

Battery installation ................................................................................................................. 19

 

6

 

Regulation ............................................................................................................................................... 20

 

6.1

 

Digital control panel: keys description ............................................................................................ 20

 

6.2

 

Display during normal operation .................................................................................................... 20

 

6.2.1

 

Functioning values display ......................................................................................................... 21

 

6.3

 

User’s parameter change ............................................................................................................... 21

 

6.4

 

Monitor mode ................................................................................................................................. 22

 

7

 

Assistance ............................................................................................................................................... 24

 

7.1

 

Gas change 

– Methane-LPG conversion ....................................................................................... 24

 

7.1.1

 

Introduction ................................................................................................................................ 24

 

7.1.2

 

Operating instruction .................................................................................................................. 24

 

7.1.3

 

Gas valve regulation .................................................................................................................. 25

 

7.2

 

Slave boards setting ....................................................................................................................... 25

 

7.2.1

 

Example of configuration of a battery with seven burner in cascade ........................................ 26

 

8

 

Safety devices ......................................................................................................................................... 27

 

9

 

Parameter list .......................................................................................................................................... 28

 

10

 

Error list ................................................................................................................................................... 33

 

10.1

 

Master board error .......................................................................................................................... 33

 

10.2

 

Slave board error ............................................................................................................................ 33

 

11

 

Electrical wiring diagram ......................................................................................................................... 34

 

Technical data ................................................................................................................................................. 36

 

 

 

Содержание CALDARIA CONDENSING 100

Страница 1: ...D LBR571 rev B 15 MCM SDC 006 CALDARIA CONDENSING 100 Instruction manual Installation and use 92 42 CEE UNI EN ISO 9001 2000 UNI EN ISO 14001 2004...

Страница 2: ...Power supply 15 5 2 Warnings 16 5 3 Electrical connections 16 5 3 1 5 3 1 Connection to temperature regulation devices 16 5 3 2 Antifreeze protection 16 5 3 3 Pump connection 16 5 3 4 Room Thermostat...

Страница 3: ...erature not exceeding 110 C UNI 10845 Italian standard for flue gas venting system for hot water boilers fired with gaseous fuels The company Robur S p A has the certification UNI EN ISO 9001 2000 CAL...

Страница 4: ...ing system and system for the production of sanitary hot water with accumulation simultaneously managing three different systems operating at three different temperatures Caldaria Condensing 100 is fi...

Страница 5: ...ers Standard condensate discharge system in the boiler Fast connection of water condensate and gas optional collectors with right and left outlet Various thermal modules and the Master control station...

Страница 6: ...t the point of sale where the product was purchased NUM DESCRIPTION 1 Packing 2 Product plate 3 Information about model gas type 4 Information about EC mark symbols 5 Lower support structure in polyst...

Страница 7: ...ion 3 2 2 Wall mounting WARNING Thermal assemblies Caldaria Condensing 100 series could be installed outdoor 3 2 2 Wall mounting The boiler must be installed on a solid masonry wall by means of hooks...

Страница 8: ...plate that is inside the shell It s important to verify the real match between available gas type and the type required by the boiler If your gas is a LPG it s important to verify the regulation of th...

Страница 9: ...aldaria Condensing 100 installed in series can be realized with the installation of a polypropylene manifold it s optional with a diameter of 125 mm with male female connections The collector was conc...

Страница 10: ...gs The condensate water produced by thermal assembly Caldaria Condensing 100 during its normal operation shall be discharged at atmospheric pressure i e by dripping into a siphon shaped container conn...

Страница 11: ...delivery 1 M in Figure 6 System return 1 R in Figure 6 To create the hydraulic connection two kits are available the first one can be used for the installation of one Caldaria Condensing 100 the seco...

Страница 12: ...perating pressure is 0 5 bar Each unit has a safety valve at 5 5 bar 3 7 2 Filling and emptying The boiler should be filled connecting the water network to any system point The boiler should be emptie...

Страница 13: ...hown in Figure 19 it is necessary to calculate the three pumps for high temperature low temperature and sanitary hot water to guarantee in any case an adequate flow for each circuit and for each unit...

Страница 14: ...Installation and user manual Error Use the Home tab to apply Titolo 1 to the text that you want to appear here 14 Figure 19 Figure 20...

Страница 15: ...lue for the pressure drop 0 100 200 300 400 500 600 700 800 0 x n 500 x n 1000 x n 1500 x n 2000 x n 2500 x n 3000 x n l h mbar Figure 22 We have to remember that the pump has to supply 2000 l h with...

Страница 16: ...the power supply cable break switch off the thermal assembly To replace it contact qualified personnel 5 3 Electrical connections 5 3 1 5 3 1 Connection to temperature regulation devices Caldaria Con...

Страница 17: ...Sanitary temperature probe S2 J11 5 6 Flow temperature probe Low SE J11 7 8 External temperature probe T1 J12 9 10 Room thermostat High T2 J12 11 12 Room thermostat Low AI J12 13 14 Analogical device...

Страница 18: ...tion of an alarm device A 220 V clear contact block output on the boiler s terminal strip allows to connect an outside sound or visual alarm device capable of highlighting any technical anomalies The...

Страница 19: ...ery installation On of the many functions included in Caldaria Condensing 100 electronics allows for the installation of several modules in series to create thermal assemblies having an overall power...

Страница 20: ...ase a value S5 Decrement It is necessary to decrease a value S6 Prog OK It is necessary to store a value U2 Luminous display Display information about boiler condition U3 Luminous display Display info...

Страница 21: ...atus e g pump not functioning e g pump functioning P 1 0 P 1 1 10 Sanitary circuit pump status e g pump not functioning e g pump functioning P 2 0 P 2 1 11 Secondary pump status e g pump not functioni...

Страница 22: ...he display returns to the parameters display mode and the T6 is displayed 6 40 If no procedures are carried out for 10 seconds after that S2 SET ESC has been pressed to modify the set point of the cor...

Страница 23: ...C 1 70 5 To exit monitor mode press S2 SET ESC If no procedures are carried out for 5 minutes the boards automatically returns to functioning display 1 80 Trough S3 S3 arrow the following values can b...

Страница 24: ...s overall length over 15 metres 7 1 2 Operating instruction 1 Shut any electric supply 2 Close the gas valve 3 Unscrew the two screws to remove the frontal panel 4 Remove the 3 screw from the gas val...

Страница 25: ...he maximum power and then change if it s necessary the Venturi regulation 7 Let the boiler arrive to the minimum power by using S5 key 8 On left of the display it will appear a L Low minimum power act...

Страница 26: ...ration of a battery with seven burner in cascade In case two blocks are present in an installation having a battery of seven burners i e seven slaves the first is made of 4 burners and the second is m...

Страница 27: ...s homologated for safety performances and with a double processor technology Such device allows to continually control both flow temperature and the Dt between flow and return of the battery element M...

Страница 28: ...NTC sensor 2 Storage heater with NTC sensor 5 Instant with flow switch 6 Storage heater with thermostat 7 P_dhw_max 1 255 230 Setting the max fan speed for dhw mode 8 T_Dhw_limit 10 C T_Dhw_max 60 Thi...

Страница 29: ...1 Attenuation_high 0 C 70 C 0 The Tset is decreased with the attenuation function only if High Temperature thermostat input is open 0 The system is turned off after thermostat opening 1 n The set poin...

Страница 30: ...If it is 0 it is used as the system pump 35 T4 frost protection 30 C 15 C 3 Temperature for starting frost protection on T4 If T4 this value or T1 5 C then the pump start If after 10 minutes T1 is not...

Страница 31: ...y Titolo 1 to the text that you want to appear here 31 restored EXCEPT GAS TYPE NUMBER par 42 and par 43 settings 42 Flow switch present on the slaves 0 1 1 0 The slave check not for the flow switch 4...

Страница 32: ...on 1 15 Max vel ventil max fan speed 230 16 Priorit riscald CH priority 0 17 Temp max CH1 80 18 Temp min CH1 50 19 Diff on CH1 CH1 on hyst 7 20 Diff off CH1 CH1 off hyst 3 21 Attenuaz CH1 CH1attenuati...

Страница 33: ...ow water flow or low system pressure 0 5 bar A05 Gas valve coil cut off Gas valve connector false contact Defective gas valve connector Limit thermostat intervention 90 C while burner was on E36 Inter...

Страница 34: ...Installation and user manual Error Use the Home tab to apply Titolo 1 to the text that you want to appear here 34 11 Electrical wiring diagram...

Страница 35: ...Installation and user manual Error Use the Home tab to apply Titolo 1 to the text that you want to appear here 35...

Страница 36: ...full load Tm 50 C 60 40 C 106 1 Efficiency at reduced load 30 80 60 C 98 7 Efficiency at reduced load 30 50 30 C 108 7 Efficiency at reduced load 30 Tm 50 C 60 40 C 106 6 Combustion efficiency 80 60...

Страница 37: ...Installation and user manual Error Use the Home tab to apply Titolo 1 to the text that you want to appear here 37 Condensate pipe mm 18...

Страница 38: ...Installation and user manual...

Страница 39: ...Installation and user manual ROBUR S p A Via Parigi 4 6 24040 Verdellino BG Tel 39 035 888 111 Fax 39 035 4821334 info robur it www robur com...

Отзывы: