Electrical hookup
20
3
3
ELECTRICAL HOOKUP
3.1
HOOKING UP THE ROOM UNIT
Figure 3.1
Example of connection of two room units, one type QAA74.611, the other (optional) type QAA55.110
A Grey connector X86 (bottom edge of RVS21.826 board)
B
Room unit 1 (QAA74.611)
C
Ambient unit 2 (QAA55.110) (optional code ODSP004)
NOTE Use shielded signal cable 3x0.75 mm
2
(2x0.75 mm
2
for QAA55.110).
Maximum total length 400 m.
Maximum length between controller and room unit 200 m.
Both room units can also be connected to connector X86.
B
C
GX1 H3 M H1
1 X86
G+ M BSB
3 2 1
1 2
A
Table 3.1
QAA74.611 and QAA55.110 (optional) room unit
connection
RVS21.826
QAA74.611
QAA55.110
BSB
3
1
M
2
2
G+
1
-