Robinson Willey ATHENA R.S. Скачать руководство пользователя страница 1

1

SERVICE & INSTALLATION

Installation and Servicing Instructions

Room Sealed Inset Live Fuel Effect Gas Fire

PRODUCT No. A99009

G.C. No. 32-170-17

‘CE MARKED’ FOR USE IN G.B. & I.E.

LEAVE THESE INSTRUCTIONS WITH THE USER

ATHENA R.S.

Содержание ATHENA R.S.

Страница 1: ...INSTALLATION Installation and Servicing Instructions Room Sealed Inset Live Fuel Effect Gas Fire PRODUCT No A99009 G C No 32 170 17 CE MARKED FOR USE IN G B I E LEAVE THESE INSTRUCTIONS WITH THE USER...

Страница 2: ...ION 5 3 FLUE TERMINAL LOCATION 6 4 CABLE FIXING 7 5 FLUE ASSEMBLY IN TIMBER FRAMED AND COMBUSTIBLE CONSTRUCTION 9 6A OVERALL FLUE LENGTH 10 6B FLUE ASSEMBLY INSTALLED 10 6C EXPLODED DIAGRAM OF FLUE CO...

Страница 3: ...extras are available Part No Combustible Wall Kit 994530 Terminal Guard 994371 Gas Safety Installation and Use Regulations 1994 as amended It is the law that all gas appliances are installed by compe...

Страница 4: ...ting type and if damaged must be replaced with the proper spare see Section 16 0 Short List of Parts 4 8 WARNING Do not operate appliance with the glass front removed cracked or broken 4 9 WARNING Do...

Страница 5: ...0 C application i e marked withthe suffix 150 If it is not feasible to cut anopening in the wallthen a rebated surroundwith a 152 mmrebate should be used to enable the heaterto be fixed to the inner f...

Страница 6: ...ight of the underside of the shelf of 125mm depth must be 130mm For shelves of greater depth allow an additional clearance of 15mm for every 25mm additional shelf depth 4 A minimum clearance to combus...

Страница 7: ...suring that the wall above the opening is properly supported using the appropriate lintel see Section 13 0 Guidance on Fitting a Lintel 7 2 Position the template supplied on the inner face of the oute...

Страница 8: ...anges of the ducts are marked TOP to indicate the way in which the ducts are to be fitted Note DO NOT remove the two middle slotted screws 8 8 Adjust the flue length First measure the wall thickness a...

Страница 9: ...cut the hole 135 mm diameter making allowances for the shrinkage of the timber frame d Measure the thickness of the combustible part of the wall and cut the flue liner to this length cutting off the e...

Страница 10: ...th the screws provided Seal the joint using the self adhesive tape provided IMPORTANT NOTES i If rear entry gas supply connection is required then it MUST be installed prior to the installation of the...

Страница 11: ...ensioning bolts j Re fit the lower air guide ensuring that the long edge with the flange points down and rests on top of the first heat exchanger g If a terminal guard is required optional extra No 99...

Страница 12: ...ove the pressure test point sealing screw and connect a pressure gauge to the test point a Light the heater Please refer to the Users Instructions Slide the control knob to the full on position marked...

Страница 13: ...heater is required see Fig 10 If there are no existingopenings or beams withineither triangle proceed withforming the opening However if openings or beams occurwithin either triangle either 1 Use the...

Страница 14: ...see Fig 12 13 5 Remove the masonry below the lintel and clear all the debris from the cavity Construct the opening to the size specified in Section 7 0 Non Combustible Wall Installation see Fig 4 A Ro...

Страница 15: ...curing screws and remove the control knob d Remove the four infill frame securing screws and remove the infill frame e Remove the lower air guide Fig 4 f Remove the Right hand side air guide g Refitti...

Страница 16: ...burner support plate in position Fig 19 g Remove the burner by sliding it towards the right 1 and then lift the left end of the burner upwards 2 see Fig 18 The burner can now be withdrawn through the...

Страница 17: ...t the yellow interrupt wires from the thermocouple b Remove the thermocouple from the bottom of the slider control FSD c Remove the thermocouple from the pilot d Refitting is the reverse procedure of...

Страница 18: ...everse procedure of removal 14 14 Removing The Thermocouple Break Micro switch a Remove the outer case as previously described in Section 14 1 b Disconnect the yellow wires from the thermocouple break...