WiNG-MGR User Guide
45
3
Web Interface
3.6. Communications
The communications options allow you to configure how the WiNG-MGR conveys its
information to individuals and other devices.
3.6.1 EIA-485
If the WiNG-MGR will communicate via the EIA-485 port, configure the necessary options
here.
Figure 3.19
EIA-485 Configuration
Option
Description
Port Function
Select an output type for the EIA-485 port - either Modbus-Slave or
BACnet-MSTP.
Default: Modbus-Slave
Baud Rate
The baud rate is selectable: 1200, 2400, 9600, or 19200. Choose the
appropriate baud rate.
Default: 9600
Slave Address
Set a slave address, from 1-254.
Set the slave address to 0 disable EIA-485 port communications.
Default: 0 (disabled)
Table 3.10
EIA-485 Configuration Options