background image

Protocol Converter

Quick Start Guide

hank you for purchasing the FDS-PC Protocol Converter. This guide 
describes how to install the Protocol Converter.

If you need further assistance, contact RLE Technologies on our 

website at 

http://www.rletech.com/ 

(go to the 

Support Link

) or by calling 

970.484.6510, Option 2

.

1

Pre-Installation

Information You Need

Consult with your IT administrator to determine the following network settings for 
the Protocol Converter:

IP address

___________________________________

Subnet mask

___________________________________

Default gateway___________________________________

Supplies You Need

18 AWG shielded, twisted-pair stranded copper wire for EIA-485 Modbus 
RTU communication. RLE recommends no more than 2,000 feet (609.6m) of 
wire at this specification. If longer runs are needed, contact RLE Technologies 
for application guidance.

Straight-through CAT5 cable for network connectivity.

Straight-through, nine-pin serial cable (temporary connection; only as 
necessary).

18 – 22 AWG ground wire.

Electrostatic discharge (ESD) protection.

2

Mounting the Protocol Converter

The Protocol Converter comes in a 19-inch (.48m), rack-mount enclosure. Rack-
mount brackets and hardware are included.

1

Attach the brackets to the sides of the Protocol Converter using the 
hardware provided.

2

Install the Protocol Converter in the rack.

3

Use the proper anchoring method to mount the unit securely.

3

Wiring the Protocol Converter

Connect the wiring for the Protocol Converter as described in the following 
subsections.

IMPORTANT

Before connecting any wiring, be sure to take precautions to protect 
the Protocol Converter from electrostatic discharge.

Power Supply and Ground Connections

1

Connect power to the Protocol Converter in one of two ways:

a

Plug the wall adapter (provided) into the power jack on the Protocol 
Converter and into a UPS outlet.

b

Connect a dedicated 24VDC power supply to the + and - terminals to the 
left of the power jack.

2

Connect an 18 – 22 AWG ground wire (not included) to the Protocol 
Converter’s ground lug and to a suitable earth ground.

Note: 

RLE Technologies recommends powering the Protocol Converter 
from a UPS (uninterruptible power supply) so the Protocol Converter 
can send alarm notifications during a power outage.

RJ45 Ethernet Connection

The Protocol Converter has an internal 10/100BaseT Ethernet port used to 
configure the Protocol Converter. The Ethernet port supports Web browser 
access, BACnet, Modbus, SNMP, and SMTP (email).

Direct connection between the Protocol Converter and a computer or laptop using 
the crossover cable (provided):

Typical Protocol Converter connection on a subnet using a hub or switch and 
straight-through CAT5 cables:

EIA-232 COM Connection

The EIA-232 port can be connected to a PC for IP configuration, firmware 
downloads, and troubleshooting. The EIA-232 is typically only used as a 
temporary connection.

Connect the straight through, 9-pin, serial cable:

Modbus EIA-485 Connections

The Protocol Converter can function as a Modbus Slave or Modbus Master over 
an EIA-485 hardware connection. The Dual Port Protocol Converter has two 
2-wire and one 2- or 4-wire EIA-485 ports for extended Modbus communication 
over multiple trunk lines.  

Standard Protocol Converter

Dual-Port Protocol Converter

T

Отзывы: