![RKI Gas Tracer Скачать руководство пользователя страница 87](http://html1.mh-extra.com/html/rki/gas-tracer/gas-tracer_operating-manual_1466731087.webp)
Gas Tracer Operator’s Manual, CSA Version
Overview • 87
Chapter 4: Using the Gas Tracer in Bar Hole Mode
Overview
This chapter explains how to operate the Gas Tracer in Bar Hole Mode. Bar Hole
Mode is used to perform consistent checks of bar holes when tracking down
underground gas leaks. When the Gas Tracer is in Bar Hole Mode, only the
combustible and oxygen channels are displayed.
If a Gas Tracer is intended for bar hole testing, it is shipped with Bar Hole Mode
enabled so that the operator must choose which operational mode to use when
the unit is turned on.
NOTE:
Units intended for bar hole testing are typically calibrated to methane.
In addition, the unit must have a %volume combustible sensor installed.
Start Up, Bar Hole Mode
This section explains how to start up the Gas Tracer in Bar Hole Mode and get it
ready for operation.
Turning On the Gas Tracer, Bar Hole Mode
WARNING:
If a CO sensor is installed, this sensor will not be active while the
Gas Tracer is in Bar Hole Mode.
WARNING:
Gas alarms are not active when the Gas Tracer is in Bar Hole
Mode.
The following description of the Gas Tracer start up sequence assumes that the
following menu items in Maintenance Mode are turned on: LNCH BRK, ID DISP,
CL RMNDR
, and BP RMNDR. If either of these items is turned off, then the
corresponding screen will not appear.
NOTE:
In order for BAR HOLE MODE to appear as a selection in the Mode
Select Screen, the L./B. MODE item in Maintenance Mode must be set to
bH or LC bH.
1. Connect the sample hose to the Gas Tracer’s quick connect inlet fitting.
2. Screw the bar hole probe onto the sample hose’s threaded fitting.