84 • Appendix A: Maintenance Mode
GasWatch 3 for CO and O
2
3. Use AIR to scroll to the item whose replacement date you want to view or change.
4. To change the replacement date:
a. With the desired item displayed, press and release POWER/MODE.
b. Press and release POWER/MODE again to set the replacement date to the current
date.
5. Use the AIR button to scroll to
ESCAPE
.
6. Press and release POWER/MODE to return to the
SEN.DATE
item in Maintenance
Mode.
7. See “Entering Measuring Mode (START)” on page 90 to enter Measuring Mode.
Performing a Bump Test (BUMP)
See “Performing a Bump Test (BUMP)” on page 37 for a description of the
BUMP
item.
Setting Alarms to Latching or Self-Resetting (LATCH)
ON
(factory setting): The GasWatch 3 remains in alarm until the alarm condition passes
and
POWER/MODE is pressed.
OFF
: The GasWatch 3 automatically resets an alarm when the alarm condition passes.
1. While in Maintenance Mode, press AIR to scroll to
LATCH
.
2. Press and release POWER/MODE. The current setting flashes.
3. Use AIR to display the desired setting.
4. Press and release POWER/MODE to save the setting and return to the
LATCH
item in
Maintenance Mode.
5. See “Entering Measuring Mode (START)” on page 90 to enter Measuring Mode.
ESCAPE
AIR
AIR AIR AIR
CO
1 . 1
2019
O2
1 . 1
2019
BATTERY
1 . 1
2019
LATCH