VOC Pro Transmitter • 31
2. Press and release the MENU button until the Unit Information screen appears.
3. Review the information displayed.
4. Press and release the MENU button to move through the Product Settings and
Configuration menu or to exit to the normal operating mode screen.
Latching and Auto Resetting Relay Settings
Relay 1 and Relay 2 can be set to latching or auto resetting. Relays set to auto resetting will
automatically deactivate when the detected gas level falls below the corresponding alarm
setting. Conversely, latching relays, once activated, MUST be manually reset at the device,
regardless of the change in gas detection level readings.
The factory default settings for Relay 1 and Relay 2 are auto resetting. During installation and
setup, Relay 1 and Relay 2 are commonly customized as the following:
Relay 1: Latching/Auto Reset Setting
1. If necessary, enter the Product Settings and Configuration menu by pressing and holding
the MENU button for 6 seconds.
2. Press and release the MENU button until the Relay 1 Latching/Auto Resetting screen
appears.
3. Use the ADD and SUB buttons to toggle between the “Auto Reset” and “Latch” options.
4. Press the MENU button to select the desired setting and to advance to the Relay 2
latching/auto reset setting screen.
NOTE:
For auto resetting alarms, the alarms will NOT deactivate until the gas level reading
at the sensor has fallen 10% below the alarm set-point. For latching alarms, the gas
level reading MUST be below the alarm set-point before the alarm can be
deactivated. The alarms will NOT activate, even in the presence of gas, until you have
exited the menu mode for approximately 1 minute.
Common Relay 1 and Relay 2 Settings
Relay
Alarm Setting
Latching/Auto Reset
Relay 1
Alarm 1
Auto Reset
Relay 2
Alarm 2
Latching