Ramp/Soak Controller
IMR02L02-E2
This manual describes the basic key operation and mode selection of the PF900/PF901.
For detailed handling procedures and various function settings, please refer to the following
separate manuals:
•
PF900/PF901 Instruction Manual (IMR02L03-E )
The above manuals can be download from our website:
URL: http://www.rkcinst.com/english/manual_load.htm
1. PARTS DESCRIPTION
RESET RUN FIX MAN HOLD
STEP R.SET PTN END
PF900
PV
TM H:M:S
SV
††††‡
‰
<<<<<<<<<<
‡
!
PTN
SEG
OUT1
1
8 8
8 8
2 3 4 5 6 7 8 9 10 11 12 ALM
DO
TS
AT
MONI
OUT2
OUT3
MODE
SET
(1)
(16)
(17)
(15)
(18)
(19)
(20)
(21)
(14)
(13)
(12)
(11)
(9)
(8)
(7)
(6)
(5)
(4)
(3)
(2)
(10)
(1) Measured value (PV)
display [Green
*]
Displays measured value (PV) or various parameter symbols.
(2) TIME display
[Orange
*]
Displays selected time unit: Hour and Minute (H: M) or Minute
and Second (M: S).
(3) SV/Timer display
[Orange
*]
Displays Set value (SV), Timer setting time or various
characters.
(4) AT/TS lamp [Green *] AT: Flashes when autotuning is activated.
(After autotuning is completed: AT lamp will go out)
TS: Lights when time signal is turned on.
(5) PTN display [Green *] Displays the pattern number in the execution: 1 to 99.
(6) SEG display [Green *] Displays the segment number in the execution: 1 to 99.
(7) Gradient state lamp
[Green
*]
Displays the state of program in process: rise, soak and fall.
The display flashes when the process is in the wait mode.
(8) Output lamp [Green *]
Lights when the output (OUT1 to OUT3) corresponding to
each lamp is ON.
Lamp indication becomes as follows for current output and
voltage current.
For an output of less than 0 %: Extinguished
For an output of more than 0 %: Lit
(9) Loader
communication
connector
Setting and monitoring on a personal computer (PC) is
possible if the controller is connected with our cable to a PC
via our USB communication converter COM-K-3 (sold
separately)
1
.
Our communication software
2
must be installed on the PC.
(10)
Monitor key
Use to switch the monitor screen. Pressing this key while any
screen other than the SV setting & Monitor mode screen is
being displayed returns to the Measured value (PV)/Set value
(SV) monitor screen.
(11)
Set key
Used for parameter calling up and set value registration.
(12)
Shift key
Shift digits when settings are changed. Used to selection
operation between modes.
(13)
DOWN key
Decrease numerals.
To scroll through numbers faster, press and hold the DOWN
key in the manual mode.
To turn back to the previous time of the program, press and
hold the DOWN key in the operation mode.
(14)
UP key
Increase numerals.
To scroll through numbers faster, press and hold the UP key
in the manual mode.
To forward the time of the program, press and hold the UP
key in the operation mode.
(15) Unit display [Green*] Displays unit:
°
C (
°
F) or %
Lights % for parameters in unit of %.
(16) Set lock display
[Orange*]
Lights when the settings are locked.
(17) ALM lamp
[Red] Lights when alarm (Event or heater break alarm [HBA]) is
turned ON.
Confirm the alarm type at the Event monitor display.
(18) Digital output lamp
[Green*]
Lights when the digital output (DO1 to DO12) corresponding
to each lamp is ON.
(19) Program pattern/
Bar graph display
[White]
Displays program patterns or bar graph for manipulated value
(MV). Red display is selectable at event or self-diagnostic
error.
*
PF901: White
1
For the COM-K, refer to COM-K Instruction Manual (IMR01Z01-E
□
).
2
Software name: WinUCI-PF900 (Only available as a download from our website.)
(20) State display lamp
[Green or Orange]
RESET: Lights in RESET mode [Orange] **
RUN: Lights in RUN mode [Orange] **
FIX:
Lights in FIX mode [Orange] **
MAN: Lights in MAN mode [Orange] **
** Other lamps light in green.
HOLD: Lights when the HOLD key is valid. [Green]
STEP: Lights when the STEP/R.SET key is set to STEP
[Green]
R.SET: Lights when the STEP/R.SET key is set to R.SET
[Green]
PTN: Lights
when
the
PTN/END key is set to PTN [Green]
END: Lights
when
the
PTN/END key is set to END [Green]
(21)
RESET: Use to switch to RESET (Control stop) mode.
RUN:
Use to switch to RUN (Program control start) mode.
Direct key
FIX:
Use to switch to FIX (Fixed set point control) mode.
MAN: Use to switch to MAN (Manual control) mode.
HOLD: Use to stop the process of the program or release the
hold function.
STEP/R.SET
STEP: Use to forward a segment of the program.
R.SET: Use to turn back to the previous parameter setting.
PTN/END
PTN:
Use to display the execution pattern setting display.
END: Use to set or release the Program end when setting
program.
2. PARAMETER SETTING MODE
2.1 Transfer to Each Mode
The controller has five different setting modes, and all settable parameters belongs to one of
them. The following chart show how to access different setting mode.
Input type and range display
This instrument immediately displays input type symbol and input range following power ON.
Example: When sensor type is K thermocouple (
−
200 to
+
1372
°
C)
2.2 Parameter Selection within Mode
SV setting & Monitor mode
It is possible to set SV which is a control target and also to monitor PV, SV, MV, etc.
*
Fix mode:
Fixed set point control mode
Parameter setting mode
It is possible to set any parameter relating to control.
*
Fix mode:
Fixed set point control mode
PF900/PF901
Quick Operation
Manual
All Rights Reserved, Copyright
2009, RKC INSTRUMENT INC.
InP
@$
K
RANGE
-200 1372
Symbol
Unit for input display
TC/RTD input:
°
C or
°
F
Voltage/Current input:
No display
Automatically
(in 2 seconds)
Input range high
Input range low
Input type symbol:
Symbol
K J T S R E b n
P
W
TC
Input type
K J T S R E B N PL
Ⅱ
W5ReW26Re
Symbol
U L
PR
PT
JP
V I
TC RTD
Voltage Current
Input type
U L PR40-20
Pt100 JPt100
V mA
Power ON
LEVEL
000:00
0
00000
TIME
000:00
0000
0
Segment level
[Factory set value: 0]
Segment time
[Factory set value: 0:00]
28
00
0:00
0000
0
28
PTN.TM 0:00
28
RPT.SG 0
28
RPT.PN 0
28
RPT.PR 0
28
CT1 0
28
CT2 0
28
EV ooooooo
28
TS oooooooo
28
MV1 0.0
28
MV2 0.0
28
WAIT OOO
PV/SV monitor
Pattern remaining time
monitor
Segment repeat
remaining time/
execution time monitor
Pattern repeat time/
execution time monitor
Total pattern repeat
remaining time/
execution time monitor
Current transformer 1
(CT1) input value
monitor
Current transformer 2
(CT2) input value
monitor
Event state monitor
Time signal state
monitor
Manipulated output
value 1 (MV1) monitor
Manipulated output
value 2 (MV2) monitor
Wait condition monitor
For details of the SV setting & Monitor mode, refer to the
PF900/PF901 Instruction Manual (IMR02L03E- )
.
Automatically
(in 2 seconds)
28
0:00
0
PV/SV monitor
Monitor mode
Press the
key can be change the
monitor displays.
Program mode
In PV/SV monitor, press the
key. The
display goes to the segment level/time setting.
28
00
0:00
0000
0
PV/SV monitor
SV
00000
Set value
[Factory set value: 0]
28
0
PV/SV monitor
28
MV 0.0
PV/SV monitor
Fix mode *
In PV/SV monitor, press the
key. The
display goes to the set value setting.
Manual mode
The
key and
key is used to
manipulate output setting in Manual mode.
Executing pattern setting
In PV/SV monitor, press the PTN/END key.
The display goes to the executing pattern
setting.
PV/SV monitor
28
00
0:00
0000
0
PTN
00001
Press the PTN/END key
Input type/Input range display
Operation mode
Change operation status/
mode such as Program/
FIX/Manual/RESET and
PID/AT, etc.
SV setting & Monitor mode
•
Mode to be selected during
normal operation
•
Changes SV, TIME, etc
•
Monitor PV, SV, MV, etc
Parameter setting mode
Create program pattern, set the
parameters such as PID and
Event, or set the parameters for
program setting such as the
time signal.
Automatically (in 4 seconds)
Power ON
Press and hold the
key
for 2 seconds or more
Press and hold the
key for 2 seconds
or more
Press and hold the
key for 2 seconds or more
Press the
key
while pressing
the
key
Press the
key while
pressing the
key for
2 seconds or more
Press the
key while
pressing the
key for
2 seconds or more
Press the
key while
pressing the
key for
2 seconds or more
Setup setting mode
In this mode, it is possible to
set setting items not stored in
the Parameter setting mode.
Some parameters are also
settable in the Engineering
mode.
Press the
key or
Press the
key while pressing the
key
Parameters in Engineering
mode are settable only when
the controller is in RESET
mode. However, it is possible
to check only the data even
in RUN mode.
Initial level engineering
mode
For details, refer to
PF900/PF901 Instruction
Manual (IMR02L03-E )
.
Engineering mode
The content relating to the
specification of this product is
set. Set meet application
requirements. For details, refer
to
PF900/PF901 Instruction
Manual (IMR02L03-E )
.
PID
PID memory
group setting
block
PID.GR
00001
PID memory group
number
LBD
GR.1 00000
LBD deadband
EVENT
Event memory
group setting
block
EV.GR
00001
Event memory group
number
EV4`
GR.1 -0050
Event 4 set value
(EV4) [low]
WAIT
Wait memory
group setting
block
WT.GR
00001
Wait memory group
number
TM.OUT
GR.1 000:00
Wait time-out set value
TM.SIG
Time signal
memory group
setting block
TS.GR
00001
Time signal memory
group number
01.E.TM
GR.1 000:00
Time signal end time
PRO.MV
Output program
memory group
setting block
P.MV.GR
00001
Output program memory
group number
P.MV3
GR.1 -005.0
Output program value 3
LV.PID
Level PID
setting block
LEVL.1
PID 00000
Level PID setting 1
LEVL.7
PID 00000
Level PID setting 7
RESET
Reset mode
setting block
SV
RESET 00000
Set value (SV) in
Reset mode
EV.GR
RESET 00001
Event memory group
number in Reset mode
FIX
Fix mode
*
setting block
SV
FIX 00000
Set value (SV) in
Fix mode
*
EV.GR
FIX 00001
Event memory group
number in Fix mode
*
MAN
Manual control
mode setting
block
PID.GR
MAN 00001
PID memory group number
in Manual control mode
EV.GR
MAN 00001
Event memory group number
in Manual control mode
EDIT
Edit block
COPY
00 ‹ 00
Pattern copy
CLR
00000
Data clear
PR.MEM
Program memory
group setting
block
PTN.NO
0000
1
Setting pattern
number
SIGNL
00000
Segment signal
28
00
0:00
0000
0
PV/SV monitor
(2 seconds or more)
PROG
Program
setting block
PTN.NO
0
1
Setting pattern
number
P.MV.GR
00000
Output program
memory group number
For details of the Parameter setting mode, refer to the
PF900/PF901 Instruction Manual (IMR02L03E- )
.