USB Communication Converter

 

COM-KG

 

IMR01Z03-E1 

All Rights Reserved, Copyright 

 2020, RKC INSTRUMENT INC.

 

In order to achieve maximum performance and ensure proper operation of the 

instrument, carefully read all the instructions in this manual. Please place the manual 

in a convenient location for easy reference. 

 

 

 

 

 
 
 

 

 

 

 

 This product is intended for use with industrial machines, test and measuring 

equipment. (It is not designed for use with medical equipment and nuclear energy 

plant.) 

  This is a Class A instrument. In a domestic environment, this instrument may cause 

radio interference, in which case the user may be required to take additional 

measures. 

  All precautions described in this manual should be taken to avoid damage to the 

instrument or equipment. If the equipment is used in a manner not specified by the 

manufacturer, the protection provided by the equipment may be impaired. 

 

NOTICE

 

  This manual assumes that the reader has a fundamental knowledge of the principles 

of electricity, process control, computer technology and communications. 

 The figures, diagrams and numeric values used in this manual are only for 

explanation purpose. 

  RKC is not responsible for any damage or injury that is caused as a result of using 

this instrument, instrument failure or indirect damage. 

  RKC is not responsible for any damage and/or injury resulting from the use of 

instruments made by imitating this instrument. 

  Periodic maintenance is required for safe and proper operation of this instrument. 

Some components have a limited service life, or characteristics that change over 

time. 

  Every effort has been made to ensure accuracy of all information contained herein. 

RKC makes no warranty, expressed or implied, with respect to the accuracy of the 

information. The information in this manual is subject to change without prior notice. 

  No portion of this document may be reprinted, modified, copied, transmitted, digitized, 

stored, processed or retrieved through any mechanical, electronic, optical or other 

means without prior written approval from RKC. 

 

1. OUTLINE 

The COM-KG is a USB communication converter for connection to USB 
communication and the following communication functions. Select a proper type 
of COM-KG according to your application. 

Loader communication:  Communication between our controllers with a loader 

  communication connector and the COM-KG. 

Serial communication (RS-485/RS-422A):   

  Communication between our controllers with a serial communication function 
  and the COM-KG. 

 
 
 
 
 
 
 
 
 
 

 

 To establish the USB communication in Windows 7, you need to 

install our dedicated USB driver on your PC. 

 

The USB driver can be downloaded from our website.

 

https://www.rkcinst.co.jp/english/download-center/ 

 

When installing the driver, a warning message may appear. 

  Continue the installation by ignoring the warning message.

 

 

  Communication in Windows 10 does not need a driver installation for 

the USB communication. 

 

1.1 Product Check

 

Before using this product, check each of the following: 

 Model code 

  Check that all of the accessories delivered are complete. 

  Check that there are no scratch or breakage in external appearance (case, 

terminal, etc). 

 
 
 
 
 

If any of the products are missing, damaged, or if your manual is 
incomplete, please contact RKC sales office or the agent. 

 

 

1.2 Model Code

 

 

COM–KG–

N

 

(1)(2) 

(1) Loader communication cable (Optional) 
N:   None 
1: W-BV-01 (1.5 m) for Loader communication 

1

 

3: W-BV-03 (1.5 m) for Loader communication 

2

 

4: W-BV-05 (1.5 m) for Loader communication

 3

 

 

(2) N (fixed) 

 

1

 

For RZ100/400, FB100/400/900, RB100/400/500/700/900, SRZ, AG500/PG500

 

2

 

For PF900/901

 

3

 

For FZ110/400/900

 

 
 

The connector on the instrument side of the W-BV-05 cable is not 
USB-compatible. Do not connect this cable to any USB devices. 

 

 

2. 

PARTS DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indication lamps 

Power indication 
lamp (PWR) 
 [Green] 

  During serial/loader communication: 

When powered from USB cable: 

Constantly on 

  In Maintenance mode: 

Flashing 

Data send lamp 
(TX) 
 [Green] 

  During transmission over the serial communication 

(RS-485/RS-422A):  

Flashing 

  During transmission over the loader communication:

 Flashing 

Data receive lamp 
(RX) 
 [Orange] 

  During reception over the serial communication 

(RS-485/RS-422A):  

Flashing 

  During reception over the loader communication: 

 Flashing 

 
 
 
 

 

 

3. MOUNTING 

 

3.1 Mounting Cautions

 

(1) Use this instrument within the following environment conditions: 

  Allowable ambient temperature: 

10 to 

55 

  Allowable ambient humidity: 

5 to 95 %RH   

 

(Absolute humidity: MAX. W. C 29.3 g/m

3

 dry air at 101.3 kPa) 

 Installation environment conditions:  

 Indoor 

use 

 

 

Altitude up to 2000 m 

(2) Avoid the following conditions when selecting the mounting location: 

  Rapid changes in ambient temperature which may cause condensation. 

  Corrosive or inflammable gases. 

  Direct vibration or shock to the mainframe. 

  Water, oil, chemicals, vapor or steam splashes. 

  Excessive dust, salt or iron particles. 

  Excessive induction noise, static electricity, magnetic fields or noise. 

  Direct air flow from an air conditioner. 

  Exposure to direct sunlight. 

  Excessive heat accumulation. 

(3) Mounting consideration 

  Install the module 200 mm away from the main power line. 

  Ensure at least 50 mm space on top and bottom of the instrument

 

for 

maintenance and operating environment. 

 

3.2 Dimensions 

 

 
 
 
 
 
 
 
 
 
 
 

 

 

3.3 DIN Rail Mounting and Removing

 

 

Mounting procedures

 

 

 
 
 

 

 

 

 

 

 

 

 

 

 

 

Removal procedures

 

 

 
 
 

 

 

 

 

 

 

 

 

 

 

Suitable for DIN-rail mounting and desktop use. 
 

 

4. WIRING 

 

 
 
 

 

4.1 Wiring Cautions 

 To avoid noise induction, keep communication signal wire away from 

instrument power line, load lines and power lines of other electric equipment. 

  If the personal computer is easily affected by noise, use the ferrite core in 

the USB cable. For an installation position of a ferrite core, please refer to 

the following figure. 

 

 

 

 

4.2

 

Wiring Connection to Establish a Loader

 

 

Communication

 

Use USB cable and loader communication cable among the PC, the COM-KG 
and our controller with a loader communication. Make sure the connectors are 
oriented correctly when connecting. 

 

Wiring example 

 
 
 
 
 
 
 
 
 
 

 

Consult with the communication instruction manual of our products for 
the communication setting on the PC and the device address for the 
loader communication. 

 

  W-BV-01 or W-BV-05 loader communication cable 

COM-KG

 

can supply USB bus power to the controller whether or not it is 

powered on or off. (When connecting an RZ series controller, the controller 
must be powered on.) 
W-BV-01:  COM-KG starts supplying USB bus power to the controller 

two seconds after the cable is connected.   

W-BV-05:  COM-KG starts supplying USB bus power to the controller as 

soon as the cable is connected. 

  W-BV-03 loader communication cable 

Controller should be always ON to use with COM-KG. 

 

Display of controller (RKC product) being powered by COM-KG: 

 

FB series,   

RB series etc. 

Displays “----” at the PV/SV monitor display. 

PF900/901 

Lights all State monitor lamps: RESET, RUN, FIX, MAN, 

HOLD, STEP.SET and PTN.END. Other displays and lamps 

are OFF. 

FZ series 

Displays “

LoAd

” at the PV monitor display.

 

Displays “-----” at the SV monitor display. 

 

The power supply function through the loader communication is not 
available on the USB hub (low power port). 

 

4.3

 

Wiring Connection to Establish a Serial 

 Communication

 

The shielded twisted pair wire must be provided by the customer. 

 

Wiring example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connector pin configuration and Signal details 

 
 

 

 

 

 

 

 

 

[RS-485]

 

[RS-422A]

 

Pin No.  Signal name  Symbol 

 

Pin No.  Signal name  Symbol 

 5 *  Unused 

 

 

Receive data 

R (B) 

 4 *  Unused 

 

 

Receive data 

R (A) 

Send data/ 

Receive data 

T/R (B)   

Send data 

T (B) 

2 Send 

data/ 

Receive data 

T/R (A)   

Send data 

T (A) 

Signal ground 

SG 

 

Signal ground 

SG 

* Do not connect wires to 4 and 5 pins. Malfunction may result. 

 

 

[RS-485]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[RS-422A]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Attention in connector wiring 

 The lead wires use the stranded wire. 

 Use the stranded wire from size 0.25 to 0.5 mm

2

 (AWG 26-20). 

 Stripping length is as follows. 

 

 

 

 

 

 

 

 

 

 

 

 

 

5. SETTING THE PROTECT MODE

 

When the COM-KG is used in the serial communication, the protect mode can be set to eliminate a response interruption of the COM-KG. To attempt protect mode 
setting, you need to switch the mode to the maintenance mode in the RKC communication protocol. Set the Protect mode referring to the following procedure as well 
as 

6. RKC COMMUNICATION PROTOCOL

You can also use our dedicated software PROTEM2 which can be downloaded from the official RKC website.

 

 

 

Setting procedures

 

 

 

 

 

Set the Maintenance mode setting (Identifier [ZZ]) to “1: Maintenance mode” from “0: Normal mode”. 

The Maintenance mode setting is accessible when Protect setting (Identifier [PZ]) is “0 (OFF)”. 
When the setting is “1” (Protect mode), reapply power to the instrument to release the Protect mode. 

 

The mode is then accessible.

 

 

 

 

 

Protect setting (Identifier [PZ]) 

0: OFF (Factory set value) 
1: Protect mode 

 

 

 

 

 

 

 
 
 
 
 
 

6. RKC COMMUNICATION PROTOCOL 

The setting of Maintenance mode needs to be done through the RKC communication (Establishing method of data link: Polling/Selecting method). 
The basic procedure follows ANSI X3.28-1976 subcategories 2.5 and A4 basic mode data transmission control procedure (Fast selecting is the selecting method used in this COM-KG). 

 

6.1 Polling

 

Polling is the action where the host computer requests of the connected COM-KG to transmit data. 

 

Polling sequence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Data link initialization 

(6)  ACK (Acknowledgment) 

(2) Send polling sequence from the host computer 

(7)  NAK (Negative acknowledge) 

(3) Data send from the COM-KG 

(8)  No response from the host computer 

(4) EOT send (Data send from COM-KG completed)  (9)  Indefinite response from the host computer 

(5)  No response from the COM-KG 

(10)  EOT (Data link termination) 

 

 

 

6.2 Selecting

 

Selecting is the action where the host computer requests of the connected COM-KG to receive data. 

 

Selecting sequence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)  Data link initialization 
(2)  Send selecting address from the host computer 
(3)  Data sent from the host computer 

For receivable/unreceivable data, refer to 

 

Numerical data handling

(4) ACK (Acknowledgment) 
(5)  NAK (Negative acknowledge) 
(6)  Indefinite response from the COM-KG 
(7)  EOT (Data link termination) 
 

 

 

Numerical data handling

 

Receivable data 

The COM-KG can receive zero-suppressed data and whole number data (data without decimal fraction). 
The number of digits varies depending on the type of identifier. (Within 7digits) 
Example: For example, even if the data 

1.5 is sent by the host as 

001.5, 

01.5, 

1.5, 

1.50, 

1.500,  

 

the COM-KG receives the data as 

1.5. 

 

When the host computer sends data containing a decimal point to the item without a decimal point, the 
COM-KG receives a message with the value that is cut off below the decimal point. 
Example: When setting range is 0 to 200, the COM-KG will receive as follows: 

Send data 

0.5 

100.5 

Receive data 

100 

 

The COM-KG

 

receives a value truncated to a specified number of decimal places.   

  The digits smaller than that will be cut off. 

Example: When setting range is 

10.00 to 

10.00, the COM-KG will receives as follows: 

Send data 

.5 

.058 

.05 

Receive data 

0.50 

0.05 

0.05 0.00 

 

Unreceivable data 

The COM-KG sends NAK when received a following data. 

Plus sign and data with a plus sign 

 

Only minus sign (without a number) 

Only decimal point (period) 

Only minus sign and a decimal point 

 

 

 

 

Connect to USB   
port of a personal 
computer 

FZ110 

Loader communication connector 

Loader communication 

cable 1.5 m (W-BV-05) 

[FZ110/400/900] 

Connect to loader   
communication 
connector 

Connect to loader   
communication connector 
of the controller

 

USB cable 1 m 

(COM-KG accessory) 

COM-KG 

 

To prevent electric shock or instrument failure, turn off the power before 
connecting or disconnecting the instrument and peripheral equipment. 

 

RKC is not responsible if this instrument is repaired, modified or 
disassembled by other than factory-approved personnel. Malfunction may 
occur and warranty is void under these conditions. 

Instruction Manual

 

Host computer   

(Send) 

COM-KG 

(Send) 

[BCC]

 

(1) 

(5) 

(3) 

(4) 

(9) 

(7) 

(10) 

[Address]  [ ID ]

 

No response 

Time 

out 

(*) 

No 

response 

Indefinite 

(8) 

(6) 

[ ID ]    [ Data ]

 

Host computer 

(Send) 

COM-KG 

(Send) 

Host 

computer 

(Send) 

(2) 

(2 digits)

 

(2 digits)

 

(7 digits)

 

(*): Approx. 3 seconds 

ID: Identifier 

(2 digits)

 

Host computer   

(Send) 

[BCC]

 

(1) 

(6) 

(3) 

(4) 

(5) 

(7) 

[Address]

 

No response 

[ ID ]    [ Data ]

 

COM-KG 

(Send) 

Host computer   

(Send) 

(2) 

(2 digits)

 

(2 digits)

 

(7 digits)

 

Host computer 
(Personal computer) 

Loader 
communication 

Serial  
communication 

*

 

COM-KG 

Controller with loader 

communication 

connector 

Controller with   

a serial comm. 

(RS-485/RS-422A)

 

(USB 
communication) 

*

 

When the COM-KG is used in the serial communication, the protect
mode can be set to eliminate a response interruption of the COM-KG.

 

Refer to 

5. SETTING THE PROTECT MODE 

for details.

 

Loader port 
shape 

USB cable (1 m) .................................................................................. 1 
Instruction Manual (IMR01Z03-E1) ...................................................... 1 

Accessories

 

USB connector 

Power indication lamp (PWR) 

Serial

 

communication 
connector 

Not used 

Not used 

Data receive lamp (RX) 

Label 

Data send lamp (TX) 

Loader  
communication 
connector 

(Unit: mm) 

38.

(24.5) 100  (33.1) 

23.2 

(5) (13.4) 

Reference plane 

Mounting 
bracket 

(A) Pull down 

(B) Push 

(C) Locked 

DIN rail 

(B) Lift and take off 

(A) Pull down 

DIN rail 

Mounting bracket 

Ferrite core * (sold separately) 

*

 

Recommended ferrite core:   

ZCAT2032-0930  
(TDK Corporation) 

USB cable 

Connect to USB   
port of a personal 
computer 

Connect to   
USB connector 

FZ400 

Shielded twisted   

pair wire 

Connect to serial 
communication 
connector 

USB cable 1 m 

(COM-KG accessory) 

RS-485/RS-422A 

Connect to   
communication 
terminals of   
the controller 

COM-KG 

Serial  
communication 
connector 


* The termination resistor (120 

) is built into the COM-KG. 

**R:  Termination resistor (Example: 120 

  1/2 W) 

If communication errors occur frequently due to the operation environment or 
the communication distance, connect termination resistor. 

Serial 

communication 

connector 

Shielded twisted   

pair wire 

T/R (A) 

T/R (B) 

SG 

Controller 

(Ex: FZ400/900) 

COM-KG* 

 

 

Communication terminals 

34 

35 

36 

T/R (A) 

T/R (B) 

SG 

R** 

Pair wire 

* The termination resistor (120 

) is built into the COM-KG. 

**R:  Termination resistor (Example: 120 

  1/2 W) 

If communication errors occur frequently due to the operation environment or 
the communication distance, connect termination resistor. 

Serial 

communication 

connector 

T (A) 

T (B) 

SG 

Controller 

(Ex: FZ400/900) 

COM-KG* 

R (A) 

R (B) 

Communication terminals 

32 

33 

34 

R (B) 

SG 

R (A) 

35 

36 

T (A) 

T (B) 

R** 

Shielded twisted   

pair wire 

Pair wire 

8 mm (Stripping length) 

Conductor cross section:  
0.25 to 0.5 mm

(AWG 26-20)

 

Connector type:   
FK-MC 0,5/5-ST-2,5 
(Products by Phoenix 
contact Ltd.) 

Change the mode to the Maintenance mode. 

Setting completed 

Select the "Protect mode" at Protect setting (Identifier [PZ]). 

Forcibly terminate the Maintenance mode and return to the Normal mode. 

When the mode is switched to the Protect mode, the instrument will forcibly terminate the Maintenance mode.

   

In the Protect mode, communication is maintained between the COM-KG and the instrument, but the communication 
between the host computer and the COM-KG through the RKC communication protocol will become unavailable.   
To release the Protect mode, turn off the power once and turn it on again. 

Connect to   
USB 
connector 