Rixson DE 4 PULL Скачать руководство пользователя страница 1

Hinge (pull) side of door mounting

Double Egress Arm
and Slide Track

AN INCORRECTLY INSTALLED OR IMPROPERLY
ADJUSTED DOOR CLOSER CAN CAUSE
PROPERTY DAMAGE OR PERSONAL INJURY.
THESE INSTALLATION INSTRUCTIONS SHOULD
BE FOLLOWED TO AVOID THE POSSIBILITY OF
MISAPPLICATION OR MISADJUSTMENT.

CA

UTION

CA

UTION

Combination Door Closer-Holder and Releasing Device
Signaled by External Detection Equipment

All dimensions are in inches and (millimeters) unless otherwise noted.

NOTE: For special applications a separate door and frame preparation template is packed with these

instructions. Use this instruction sheet for installation sequence and closer adjustments only.

Requirements:

Units are handed. Hand of unit and hand of door must be the
same.
Door must be hung on butt hinges or ¾” (19) offset pivots.
Door thickness must be 1¾” (44) minimum 2¼” (64) maximum.
Door must swing freely through the entire opening and closing
cycle before beginning the installation procedure.
Frame face must be a minimum of 2” (51).

Use of an auxiliary door stop, by

others, is required.

Backplate
Mtg Screw (5)

Arm Screw

Track Mtg
Screw (3)

Cover

Backplate

Hook-up Board

Main Arm

Slide Track

Concealed Wired Unit Shown

Cover Mtg
Screw (3)

RH - Right Hand Door
LHR - Left Hand Reverse

Left Hand Door - LH

Right Hand Reverse - RHR

Installation Instructions

80-9372-0094-015 (02-09)

Selective Hold Open
Cam & Switch
Assembly

Closer/Holder

Test Switch
Access Tube

Slide Assembly

9/32” (7 mm);
3/8” (9.5 mm) dia. x
3/8” (9.5 mm) deep on
door opposite to closer

Standard

Optional

Through-bolts and
grommet-nuts

All

Preparation for Fasteners

Door or Frame

Fasteners

Drill-Sizes

1/4” - 20 machine

screw

Metal

Drill: #7 (0.201” dia.)
Tap: 1/4” - 20

Sleeve nuts and bolts

Hollow

Metal

9/32” (7 mm) through;
3/8” (9.5 mm) door face
opposite to closer

Aluminum

or Wood

3/8” (9.5 mm) through

Ceiling clearance must be a minimum of 4” (102).

Power input to unit must be of the same voltage as that stated
on the unit.
Unit to be mounted on interior of building in dry environment,
maximum humidity of 95%.
See NFPA70 for wiring requirements and NFPA72 for alarm
system requirements.

Ceiling Line

2

(51)

4

(102)

Min

Min

Support Unit

Models

DE 4 PULL

Selective Multipoint

Hold Open

Note:

Only for

hinge side

frame reveals

of 1/8” to 3”

(3mm to

76mm)