RIX Industries
MAN-2PS2B-N2
Page 7
4.4
Control logic Description
The following explains the logic sequence as reflected on the electrical schematic (
Figure 16
in
Appendix):
1.
With power applied to the unit and the HOA selector switch (HOA) in HAND, push
the START pushbutton.
2.
The two pressure switches, suction (PSIL) and discharge (PSR) are connected in
series to the motor controller. If the suction pressure is high enough to close the
suction pressure switch, and the discharge switch remains closed (pressure below
the switch "closed" setting) the compressor will start.
3.
Current passes through the two closed pressure switches, the closed time delay
relay (TDR), and energizes the starter coil (C-1). The starter coil starts the main
drive motor. The fan motor and hour meter also operate at this point. The green
light (LG) will energize indicating the compressor is running. Tripping of either the
suction or discharge switch will break current to the coil (TDR) which will stop the
drive motor.
4.
The compressor may also be run in the automatic mode by selecting AUTO on the
HOA switch. All features are the same as described above except that after the inlet
or discharge switch shut down the unit, the compressor will automatically restart
when the switches are moved to the "closed" setting. The compressor will continue
cycling until the selector switch is moved to either HAND or OFF.
5.
The unit may be stopped at any time by switching the HOA to OFF.
4.5
Safety Device Set Points
The following safety devices have been provided at the set points noted below. Pressure switch
settings may be adjusted to User’s needs but set points shall not exceed the design constraints given
in
Compressor Specifications
. Do not adjust relief valve settings.
Device
Stage
Set Point
Function
Relief Valve
Suction
75 psig
Relieve excess
pressure build up
Interstage
700 psig
Discharge
2200 psig
Motor Overload
N/A
Motor FLA
Shutoff
Pressure Switch
Suction
30 falling
Shutoff
Discharge
2200 rising
Shutoff
Содержание 2PS-H-N2
Страница 36: ...RIX Industries MAN 2PS2B N2 Page 28 FIGURE 1 COMPRESSOR CROSS SECTION FASTENER DETAIL...
Страница 37: ...RIX Industries MAN 2PS2B N2 Page 29 FIGURE 2 COMPRESSOR CROSS SECTION PUMP DETAIL...
Страница 38: ...RIX Industries MAN 2PS2B N2 Page 30 FIGURE 3 1ST STAGE VALVE DETAIL...
Страница 39: ...RIX Industries MAN 2PS2B N2 Page 31 FIGURE 4 2ND STAGE VALVE DETAIL...
Страница 40: ...RIX Industries MAN 2PS2B N2 Page 32 FIGURE 5 EXTERIOR FASTENER DETAIL...
Страница 41: ...RIX Industries MAN 2PS2B N2 Page 33 FIGURE 6 MOTOR AND CONTROL BOX MOUNTING...
Страница 42: ...RIX Industries MAN 2PS2B N2 Page 34 FIGURE 7 SUCTION PLUMBING DETAIL...
Страница 43: ...RIX Industries MAN 2PS2B N2 Page 35 FIGURE 8 INTERSTAGE PLUMBING DETAIL...
Страница 44: ...RIX Industries MAN 2PS2B N2 Page 36 FIGURE 9 FINAL DISCHARGE PLUMBING DETAIL...
Страница 45: ...RIX Industries MAN 2PS2B N2 Page 37 FIGURE 10 COOLING FAN SUB ASSEMBLY DETAIL...
Страница 46: ...RIX Industries MAN 2PS2B N2 Page 38 FIGURE 11 BELT INSTALLATION DETAIL...
Страница 47: ...RIX Industries MAN 2PS2B N2 Page 39 FIGURE 12 GUARD MOUNTING DETAIL...
Страница 48: ...RIX Industries MAN 2PS2B N2 Page 40 FIGURE 13 CONTROL BOX DETAIL 1 OF 2...
Страница 49: ...RIX Industries MAN 2PS2B N2 Page 41 FIGURE 14 CONTROL BOX DETAIL 2 OF 2...
Страница 50: ...RIX Industries MAN 2PS2B N2 Page 42 FIGURE 15 CONTROL BOX WIRING DIAGRAM...
Страница 51: ...RIX Industries MAN 2PS2B N2 Page 43 FIGURE 16 ELECTRICAL SCHEMATIC...
Страница 52: ...RIX Industries MAN 2PS2B N2 Page 44 FIGURE 17 FLOW SCHEMATIC...
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......