Rittal Liquid Cooling Package
39
13 Further technical information
EN
13.2.7 Cooling output at a room temperature of
24°C
10 kW devices 3311.610/710/810/910
Cooling output, sensible [kW]
15
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
20
20
21
21
22
22
Water volume [l/min]
28
32
34
36
40
50
Volumetric airflow [m
3
/h]
3200
3200
3200
3200
3200
3200
Air outlet from LCP Hybrid [°C]
23
23
23
23
23
23
Air inlet to LCP Hybrid [°C]
38
38
38
38
38
38
T air [K]
15
15
15
15
15
15
Tab. 34: Cooling output at partial load and a
T air of 15 K
Cooling output, sensible [kW]
18
18
18
18
18
18
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
19
19
20
20
20
21
Water volume [l/min]
40
45
50
55
65
75
Volumetric airflow [m
3
/h]
4500
4500
4500
4500
4500
4500
Air outlet from LCP Hybrid [°C]
23
23
23
23
23
23
Air inlet to LCP Hybrid [°C]
35
35
35
35
35
35
T air [K]
12
12
12
12
12
12
Tab. 35: Cooling output at full load and a
T air of 12 K
Cooling output, sensible [kW]
20
20
20
20
20
20
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
20
20
20
20
20
21
Water volume [l/min]
37
40
45
55
75
75
Volumetric airflow [m
3
/h]
4000
4000
4000
4000
4000
4000
Air outlet from LCP Hybrid [°C]
23
23
23
23
23
23
Air inlet to LCP Hybrid [°C]
38
38
38
38
38
38
T air [K]
15
15
15
15
15
15
Tab. 36: Cooling output at full load and a
T air of 15 K
Cooling output, sensible [kW]
5
5
5
5
5
5
5
Inlet temperature [°C]
12
13
14
15
16
17
18
Return temperature [°C]
24
23
23
22
22
22
22
Water volume [l/min]
7
8
8
11
13
16
18
Tab. 37: Cooling output at partial load and a
T air of 12 K