35
13 Further technical information
EN
13.2.5 Cooling output at a room temperature of
22°C
10 kW devices 3311.610/710/810/910
Cooling output, sensible [kW]
20
20
20
20
Inlet temperature [°C]
12
13
14
15
Return temperature [°C]
18
18.5
18
19
Water volume [l/min]
48
52
68
75
Volumetric airflow [m
3
/h]
4000
4000
4000
4000
Air outlet from LCP Hybrid [°C]
21
21
21
21
Air inlet to LCP Hybrid [°C]
36
36
36
36
T air [K]
15
15
15
15
Tab. 20: Cooling output at full load and a
T air of 15 K
Cooling output, sensible [kW]
5
5
5
5
5
5
5
5
Inlet temperature [°C]
12
13
14
15
16
17
18
19
Return temperature [°C]
20
20
20
20
20
20
21
21
Water volume [l/min]
9
11
13
15
19
22
28
40
Volumetric airflow [m
3
/h]
1300
1300
1300
1300
1300
1300
1300
1300
Air outlet from LCP Hybrid [°C]
22
22
22
22
22
22
22
22
Air inlet to LCP Hybrid [°C]
34
34
34
34
34
34
34
34
T air [K]
12
12
12
12
12
12
12
12
Tab. 21: Cooling output at partial load and a
T air of 12 K
Cooling output, sensible [kW]
5
5
5
5
5
5
5
5
Inlet temperature [°C]
12
13
14
15
16
17
18
19
Return temperature [°C]
20.5
20
20
20
20
20.5
21
21
Water volume [l/min]
9
11
13
15
19
22
28
40
Volumetric airflow [m
3
/h]
1100
1100
1100
1100
1100
1100
1100
1100
Air outlet from LCP Hybrid [°C]
22
22
22
22
22
22
22
22
Air inlet to LCP Hybrid [°C]
37
37
37
37
37
37
37
37
T air [K]
15
15
15
15
15
15
15
15
Tab. 22: Cooling output at partial load and a
T air of 15 K
Cooling output, sensible [kW]
10
10
10
10
10
Inlet temperature [°C]
12
13
14
15
16
Return temperature [°C]
18
18
19
19
19
Water volume [l/min]
24
28
30
37
45
Tab. 23: Cooling output at full load and a
T air of 12 K