Rittal Liquid Cooling Package
27
11 Technical specifications
EN
11
Technical specifications
11.1 10 kW versions
Technical specifications
Description/Model No.
TopTherm LCP Hybrid / 3311.610 (2000 mm high, 600 mm wide)
Description/Model No.
TopTherm LCP Hybrid / 3311.710 (2200 mm high, 600 mm wide)
Description/Model No.
TopTherm LCP Hybrid / 3311.810 (2000 mm high, 800 mm wide)
Description/Model No.
TopTherm LCP Hybrid / 3311.910 (2200 mm high, 800 mm wide)
Dimensions and weight
3311.610
3311.710
3311.810
3311.910
(Width x height x depth [mm])
600 x 2000 x 105
600 x 2200 x 105
800 x 2000 x 105
800 x 2200 x 105
Usable U
42
47
42
47
Opening angle of door
135°
135°
135°
135°
Weight [kg]
76
78
78
81
Cooling circuit
Cooling medium
Water (see Internet for specifications)
Cold water inlet temperature [°C]
+7…+30 and at least 3 K above the dew points of the ambient and flowing air
Permissible operating pressure PS1
[bar]
6
Fill quantity of heat exchanger [l]
8
Max. volumetric flow of water [l/min]
70
Fill quantity of heat pipe with R134a
[kg]
0.65
Water connection
DN 25 (G1")
Rated cooling output
Cooling output, sensible [kW]
10
Volumetric flow of cooling water
[l/min]
30
Cold water inlet temperature [°C]
+15
Volumetric flow of air [m
3
/h]
2700 (air from IT equipment)
Room air temperature [°C]
+24 (air outlet temperature from LCP Hybrid)
Relative humidity [%]
43
Other information
Noise level
Depends on the configuration of the IT rack with equipment
Colour
RAL 7035
Tab. 3:
Technical specifications for 10 kW versions