Rittal Liquid Cooling Package
15
5 Assembly and siting
EN
Remove the server enclosure door from the enclosure,
including the hinges, to the rear.
If divided rear doors were fitted to the server enclo-
sure, the lock pieces in the centre will additionally need
to be removed.
5.2.4
Fit the door latch mechanisms
To lock the LCP Hybrid with the server enclosure, the
four lock pieces included with the supply are mounted
on the handle side.
Fig. 14:
Lock piece
Rotate the first lock piece so that the "L" marking is
legible.
Screw the lock piece through the bottom opening on
one of the four mounting positions in the server enclo-
sure.
In the same way, attach the three other lock pieces to
the lock side of the server enclosure.
5.2.5
Fit the LCP Hybrid
Leaving the LCP Hybrid in its packaging, position it be-
hind the server enclosure on which it is to be fitted.
Open the packaging.
With at least two people, lift the LCP Hybrid out of the
packaging and set it upright.
Rotate the LCP Hybrid on the mounting aid, in such a
way that the mounting points and the cooling water
connections are on the right-hand side.
Push the LCP Hybrid against the server enclosure on
the mounting aid, and align it in such a way that the
mounting points in the door hinge of the LCP Hybrid
are aligned with the corresponding openings in the
server enclosure.
Fig. 15:
Mounting the LCP Hybrid – Exterior
Key
1
Server enclosure
2
Mounting point
3
Door hinge
Screw the LCP Hybrid onto the four mounting points
to which standard server enclosure door hinges are
attached.
The LCP Hybrid is additionally screw-fastened to the in-
side of the server enclosure at the top and bottom.
Swing the LCP Hybrid away from the server enclosure
to give you access to the rear of the server enclosure.
Secure the LCP Hybrid on the inside top using two
screws included with the supply.
Note:
At least two people must work together to in-
stall the LCP Hybrid.
M
D
= 9 Nm
4 x
M6 x 12
1
3
2