5 Installation
EN
16
Rittal enclosure cooling unit
Fig. 14:
Lock home the clip behind the cut-out (for SK 317880x
and SK 317980x)
For SK 31848x0: Push the cooling unit into the mount-
ing cut-out at the top until both clips behind the cut-
out audibly lock home.
Fig. 15:
Lock home the clips behind the cut-out (for
SK 31848x0)
Similarly, at the top, screw two grub screws into the
blind rivet nuts in the rear corners of the cooling unit
(torque = 5 Nm).
Fig. 16:
Screw the upper grub screws into place
Attach the two corner brackets with nuts to the grub
screws at the top and secure (torque = 5 Nm).
Fig. 17:
Secure with corner brackets at the top
In the same way, attach the two corner brackets with
nuts onto the grub screws at the bottom and secure
(torque = 5 Nm).
Fig. 18:
Secure with corner brackets at the bottom
Insert one spring clip half-way up the rear of the cool-
ing unit on both the left and right.
Fig. 19:
Secure with spring clips
5.3.5
Internal mounting of the cooling unit
SK 317880x and SK 317980x
Grasp hold of the recessed handles on the left and
right of the louvred grille and pull the louvred grille gen-
tly upwards out of the device mounting clips.
CLICK!
CLICK!
CLICK!