Rittal enclosure cooling unit
15
5 Installation
EN
Using the diagrams in section 12.1 "Representation of
mounting cut-outs", calculate the required dimensions
for your mounting cut-out.
Make the required mounting cut-out.
Carefully deburr the cut-out to prevent injuries caused
by sharp edges.
5.3.4
External mounting of the cooling unit
Screw two grub screws into the blind rivet nuts in the
corners at the bottom rear of the cooling unit (torque
= 5 Nm).
Fig. 10:
Screw the lower grub screws into place
For SK 317880x and SK 317980x: Insert a locator clip
at the top left so that it latches securely home into the
cooling unit.
Fig. 11:
Insert the locator clip (for SK 317880x and
SK 317980x)
For SK 31848x0: Insert two locator clips at the top so
that they latch securely home into the cooling unit.
Fig. 12:
Inserting the locator clips (for SK 317980x)
These clips will prevent the cooling unit from falling out
of the mounting cut-out later on before it is properly
secured using the corner brackets with nuts.
Lift up the cooling unit, and initially set it down with the
two outside lower grub screws resting on the enclo-
sure door or side panel.
Fig. 13:
Position the cooling unit and push it home
For SK 317880x and SK 317980x: Push the cooling
unit into the mounting cut-out at the top until the clip
behind the cut-out audibly latches home.
Caution!
There is a risk of injury on sharp cut-outs
which have not been properly deburred,
especially while mounting the cooling
unit.
Note:
In these instructions, we have only provided
images of units SK 31848x0 in cases where
assembly deviates from the illustration given.
1.
2.
CLICK!
Note:
In the subsequent step, take care to ensure
that the cooling unit only rests on the grub
screws, never on the seal, otherwise the seal
could become damaged.
1.
2.
CLICK!