PSM MID measuring module for CMC III
DK 7859.312DK 7859.332
Montage-, Installations- und BedienungsanleitungAssembly and operating instructions
Страница 1: ...PSM MID measuring module for CMC III DK 7859 312 DK 7859 332 Montage Installations und Bedienungsanleitung Assembly and operating instructions ...
Страница 2: ...II subsequently called PSM MID measuring module We wish you every success Your Rittal GmbH Co KG Rittal GmbH Co KG Auf dem Stützelberg 35745 Herborn Germany Tel 49 0 2772 505 0 Fax 49 0 2772 505 2319 E mail info rittal de www rittal com www rittal de We are always happy to answer any technical ques tions regarding our entire range of products ...
Страница 3: ...a CMC III Processing Unit 10 7 Operation 11 7 1 Operating and display elements 11 7 2 LED displays 11 7 2 1 Multi LED displays 11 7 2 2 Display of the LEDs above the MID displays 11 7 2 3 Displays of the LEDs on the CAN bus connection 11 7 3 Description of operation 12 7 3 1 General notes 12 7 3 2 Values for energy billing 12 7 4 Operation from the operating elements on the front 12 7 4 1 Settings...
Страница 4: ...nd must al ways be available and on hand for the operating and maintenance personnel 1 3 Symbols in these operating instructions The following symbols are used in this documentation This symbol indicates an Action Point and shows that you should perform an operation procedure 1 4 Other applicable documents Installation and Short User s Guide CMC III Processing Unit Assembly and Operating Instructi...
Страница 5: ...ing module that are not described in this manual or in the associated manuals The operational safety of the PSM MID measuring module is guaranteed only for its approved use The technical data and limit values stated in the techni cal specifications may not be exceeded under any circumstances In particular this applies to the specified ambient temperature range and IP degree of protection The PSM M...
Страница 6: ...f the calibration end date print ed on the measuring module is not permitted The unit is state of the art and built according to rec ognised safety regulations Nevertheless improper use can present a hazard to life and limb of the user or third parties or result in possible impairment of the system and other property The unit should thus only be used properly and in technically sound condition Any...
Страница 7: ...he unit for any damage that has occurred during transport Remove the unit from the packaging Note After unpacking the packaging materials must be disposed of in an environmentally friendly way They can consist of the follow ing materials Polyethylene film PE film cardboard Note Damage and other faults e g incomplete delivery should immediately be reported to the shipping company and to Rittal GmbH...
Страница 8: ...e Interfering electrical installations high frequency should be avoided 5 2 Assembly procedure 5 2 1 Notes on assembly The PSM MID measuring module must not be in stalled in vertical position and also not upside down in the enclosure Ensure good access to the front of the unit so that the display is easy to read 5 2 2 Assembly of the PSM MID measuring module Fasten the PSM MID measuring module as ...
Страница 9: ...cable set CEE 32 A Observe the pin assignment of the connections identical for the inputs and the outputs After making the connection the status screen and the MID displays of infeeds 1 and 2 show briefly the software version of the PSM MID measuring module on the main display of the measuring module fig 4 item 6 The unit is operational after a short delay 6 3 Installation procedure Fig 3 Connecti...
Страница 10: ...de an appropriate cable clamp for all connection cables 6 4 Connection to a CMC III Processing Unit A further configuration of the PSM MID measuring module is possible from a web site when the unit is connected to a CMC III Processing Unit Connect the PSM MID measuring module using a CAN bus connection cable with a CAN bus interface of the CMC III Processing Unit or of the neighbour ing component ...
Страница 11: ...n be read on the multi LED Continuous illumination Tab 1 Multi LED continuous illumination Flashing codes Tab 2 Multi LED flashing codes 7 2 2 Display of the LEDs above the MID displays The two LEDs above the MID displays flash cyclically during the measurement and are used for the con sumption display 7 2 3 Displays of the LEDs on the CAN bus connection A red and a green LED are located on the CA...
Страница 12: ...on 7 4 1 Settings using the configuration menu All categories can be set only via the CMC III Processing Unit All energy values that the customer can reset Keep the Esc key pressed fig 4 item 4 Also press the Down key for approx 3 seconds fig 4 item 8 The Reset to Factory Default prompt appears in the main display Use the Down key to select the Yes row and press the Return key to confirm the selec...
Страница 13: ...ange the value has been se lected the or symbols are prefixed or suffixed respectively in the main display The Up and Down keys can be used to change the value iteratively Example Use the Down key on the main screen to select the Circuit 1 Press the Return key The Circuit 1 Menu menu appears Use the Down key to select the Phase 1 Informa tion entry Press the Return key The Circuit 1 Phase 1 menu a...
Страница 14: ...try in the left hand tree structure In the following sections 7 5 1 Device to 7 5 3 Circuit 2 only those parameters for which you can make changes are described in detail There are also dis play values used only for information purposes 7 5 1 Device General settings for the PSM MID measuring module are made at the Device level Tab 5 Settings in the Device level Parameters that provide detailed inf...
Страница 15: ... measuring module Tab 7 Displays in the Unit main level The following parameters are also displayed in the as sociated sublevels for infeed 1 Tab 8 Displays in the associated sublevels Neutral Current sublevel You can set the following parameters for the neutral conductor current in the Neutral Current sublevel Note The Current row and the Σ symbol of the neutral conductor current are displayed in...
Страница 16: ...imit of the voltage value of phase L1 for which a warning message is is sued SetPtLow Warning Lower limit of the voltage value of phase L1 for which a warning message is is sued SetPtLow Alarm Lower limit of the voltage value of phase L1 for which an alarm message is issued Hysteresis If one of the upper limit values is overshot SetPtHigh or one of the lower limit val ues is undershot SetPtLow a w...
Страница 17: ... match fully those for infeed 1 see section 7 5 2 Circuit 1 Parameter Explanation Power Factor Actual power factor Active Power Actual active power Apparent Power Actual apparent power Reactive Power Actual reactive power Active Energy Actual active energy Apparent Energy Actual apparent energy Note You can make the same settings for phases L2 and L3 in the appropriate levels as for phase L1 ...
Страница 18: ...nce Because the unit is largely maintenance free the maintenance of the unit is largely limited to the in spection and cleaning tasks 8 2 4 Recalibration After expiration of the calibration end date printed on the measuring module the unit must be recalibrated if it is still to be deployed for billing purposes If necessary contact Rittal for a recalibration of the unit 8 2 5 Test procedure To test...
Страница 19: ...ce is not used for a long period Rittal rec ommends that it is disconnected from the mains pow er supply and protected from dampness and dust 9 2 Disposal Because the PSM MID measuring module consists primarily of the housing and circuit board compo nents the device must be sent to the electronic recy cling for disposal ...
Страница 20: ...e connection cables on a PSM MID measuring module 10 3 Other possible error sources Under some circumstances one of the two above mentioned error messages is displayed although you have used the correct connection cable This can be the case when the voltage supply to the device at the Infeed 1 connection has already been established and you then want to connect further cables In this case disconne...
Страница 21: ...infeed Acquired values per phase Voltage V current A frequency Hz active power kW active en ergy kWh apparent power VA apparent energy VAh reactive power Var power factor cosPhi neutral conductor measurement determination of load unbalance Voltage V measurement range 180 V to 260 V Voltage V resolution 0 1 V Voltage V accuracy 2 Current A measurement range 0 A to 18 A 0 A to 35 A Current A resolut...
Страница 22: ...ons Protection class Class 3 Level of contamination 2 Protection category IP 51 according to IEC 60 529 Storage temperature 25 C to 55 C Ambient operating temperature 25 C to 55 C Operating humidity range 20 to 90 relative humidity non condensing Technical specifications PSM MID measuring module for CMCIII ...
Страница 23: ... available at the Internet address specified in section 13 Customer service addresses Tab 18 Accessories PSM MID M16 DK 7859 312 Tab 19 Accessories PSM MID M32 DK 7859 332 Designation Model No DK Connection cable set 1 x input 3 m 1 x output 1 m CEE IEC 60 309 2 x required when both infeeds are used 7859 315 Connection cable set for PSM busbars with Wago X Com connectors 2 x required when both inf...
Страница 24: ...ing module for CMC III 13 Customer service addresses For technical questions please contact Tel 49 0 2772 505 9052 E mail info rittal de Homepage www rittal com For complaints or service requests please contact Tel 49 0 2772 505 1855 E mail service rittal de ...
Страница 25: ......