● Battery voltage (mV).
The system is fitted with two batteries (12 V / 2.2 Ah) which are connected in
series.
● Inside temperature of the system (°C).
● Internal resistance of the battery (mOhm).
If the internal resistance of 1200 mOhm is exceeded, the batteries must be
changed.
Previous menu item
Exit menu
Next menu item
Activate submenu
The current values are determined. The value indicated
counts up to approx. 76 (progress bar). No further oper-
ation is possible at this stage.
Please wait for this stage to be concluded.
Has no function
Exit display
Has no function
Exit display
8.12.4
Measuring alarm device
The alarm device must be measured so that a wire break or short circuit can be
detected via the cyclically determined values. In the menu "Measuring alarm
device", the current measured value of the terminating resistor at connection
"external AD" is cyclically determined and shown as an AD value. The limit values
resulting from this for the monitoring are calculated and displayed automatically. The
limit values can be confirmed and saved with
[Reset PS]
"Adopt current value". The
menu is exited with
[Reset]
"Exit display" without saving the displayed values.
Previous menu item
Exit menu
Next menu item
Activate submenu
The current values are determined. The value indicated
counts up to approx. 55 (progress bar). No further oper-
ation is possible at this stage.
Wait for this stage to be concluded.