Fig. 16: Potential-free contacts
INFORMATION
Make sure, at an early stage, that the cabinet to be protected meets all of the
requirements in regard to space needs, tightness and mounting options, so that the
system can be installed in a proper functional manner.
INFORMATION
Be sure to keep the packaging the system came in. The system can only be sent
for maintenance or repair in the special original packaging it came in or in pack-
aging equivalent to this.
5.2.1
Installation instructions
L
WARNING
Danger due to faulty installation!
Non-horizontal installation of the system results in the extinguishing agent not being
fully discharged and the failure message
„Extinguishing agent loss”
being dis-
played.
● Mount the system in a horizontal position (using a spirit level for alignment).
L
WARNING
Risk of injury from the installation of the system in unsuitable control
cabinets!
Installing the system in non-closed control cabinets, such as those without doors or
side parts, can lead to the uncontrolled dissemination of smoke and fire, as well as
fires not being detected, the extinguishing agent not be disseminated in a controlled
manner and fires not being extinguished. This can lead to serious injuries and even
death.
● Only use the system in closed control cabinets.
Mounting and installation
Operating Instructions / DET-AC III Slave / 916007 / 05-2016 / en_US
32