3.3
Connections
Fig. 5: "AT3 connection technology" card (left) and "NW network interface" card
(right)
1 Connecting terminal for relay output
„
Pre-alarm
2 Connecting terminal for relay output
„
Fire alarm
”
3 Connecting terminal for relay output
„
Extinguishing
”
4 Connecting terminal for relay output
„
Common failure
”
5 Plug (RJ12) for door contact switch connection
6 Plug (RJ12) for connection to Rittal Monitoring System CMC (
„
failure
”
)
Chapter 3.3.3 „Interfaces to the Monitoring System CMC III / CMC
7 Plug (RJ12) for connection to Rittal Monitoring System CMC (
„
fire alarm
”
)
Chapter 3.3.3 „Interfaces to the Monitoring System CMC III / CMC
8 Plug (RJ12) for connection to Rittal Monitoring System CMC (
„
pre
‑
alarm
”
)
Chapter 3.3.3 „Interfaces to the Monitoring System CMC III / CMC
9 Connection for networking "DET-AC III Master - DET-AC III Slave" (RJ12-DEC)
Chapter 3.3.8 „Connection for networking” on page 26
Chapter 3.3.4 „Connection of external alarm device”
(delivery with terminating resistor 47
Ω
and diode 1N4007)
11 Connection for external fill level monitoring and triggering of external tank (only
activated in the aspirating smoke detection system EFD III)
12 Plug for manual call point (delivery with terminating resistor 1,8 k
Ω
)
3.3.5 „Manual call point connection” on page 25
13 Door contact plug 2 (delivery with two terminating resistors: 1,8 k
Ω
and 470
Ω
)
Chapter 3.3.2 „Door contact switch” on page 24
14 Power supply (U
B
Chapter 3.3.6 „Power supply” on page 25
Chapter 3.3.7 „USB port” on page 26
16 CAN bus CMC III interface (RJ45)
Chapter 3.3.3 „Interfaces to the Monitoring
Structure, function and connections
Operating Instructions / DET-AC III Slave / 916007 / 05-2016 / en_US
22