Installing Bus Devices
Page
47
Lumin8
BUS (Serial) connection to ProSYS FreeCom
BLK
COM
BELL
+
YEL
GRN
+
-
HOLD
GRN
YEL
PRO BUS
LuMIN8 Sounder
ProSYS FreeCom
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
DIPSWITCH
SCB/SAB
A1
A2
A3
BUS/STD
PRO/ACT
MON/NM
TMF/EXT
Sounder defined
as unit No. 2
BUS
Connecting Bus Detectors
Up to 32 addressable bus detectors can be assigned to the LightSYS. Bus detectors can be
wired to the main bus or to a Bus Zone Expander (BZE).
For full installation instructions refer to the instructions supplied with each bus detector.
To connect bus detectors to the main LightSYS bus
1.
Set the bus detector ID number (1-32) using the detector's DIP switches.
Note:
For WatchOUT, LuNAR, and WatchIN set the switch that defines the detector
operation mode to bus mode.
2.
Wire the bus terminals AUX(RED), COM (BLK), BUS (YEL) and BUS (GRN) to the
LightSYS bus.
Note:
For maximum operation stability, it is best NOT to exceed a total 300 meters (1000
feet) of wiring from the bus detector to the LightSYS panel.
To connect bus detectors using a Bus Zone Expander (BZE)
Important Note:
Connecting bus zones to the LightSYS using the bus zone expander can only be done
using Bus Zone Expander version B and later, PN RP128EZB000B.
1.
Set the BZE ID number (1-3) using the DIP switches SW1 1-3.
2.
Set the BZE SW2-3 to
ON
position.
3.
Wire the BZE terminals marked as
TO PANEL
to the LightSYS bus.
4.
Set the bus detector ID number (1-32) using the detector's DIP switches.
Note:
Do not repeat the same ID twice on the same BZE.
5.
Wire each detector's bus terminals to the relevant BZE's terminals marked as
TO
DEVICE
.(see figure below)