If a zone in the Soak Test list has an alarm during the 14-day period, the
keypad indicates to the user that the test has failed. After the user looks at
the View Fault option (described in the
LightSYS User's Manual
), the fault
message will be erased. This will be indicated in the event log, but no
alarm will be generated. The alarmed zone's 14-day Soak Test period is
then reset and restarted..
To set up a Soak-Test. [LightSYS]
1.
From the Install menu, press quick keys
. The
following display appears:
ZONES FOR TEST:
01) NONE
2.
To put a zone on Soak Test, press
. The following display
appears:
LOCATION 01:
ZONE: 00-32
3.
Press the keys as per the zone number (e.g. 01 for zone 1
)
4.
Press
to confirm and display the initial menu.
5.
To add a second zone for Soak Test, press and repeat the
procedure above, -OR Press the
key to return to the
previous menu.
Cross Zones
Default:
No cross zoning
The Zone Crossing menu is used for additional protection from false alarms and contains
parameters that enable you to link together two related zones. Both must be violated within a
designated time period (between 1 and 9 minutes) before an alarm occurs.
This type of linking is used with motion detectors in
hostile
or
false-alarm prone
environments.
The LightSYS allows 10 unique sets of zone links (pairs of zones), which can be manually
specified, as required. Zones crossed with themselves are valid pairs. They need to register a
violation twice to trigger the alarm. This process is known as Double Knock. You may want to
establish a number of zone links, but leave them deactivated at this time (see below).