![Ripley PIT-1T Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/ripley/pit-1t/pit-1t_instructions_1463918001.webp)
PIT
Probe Insertion Tools
PIT 1T
Note: These tools have been specifically designed for the installation and removal of 15 to 35 KV Load Break
Probes.
FEATURES AND BENEFITS
•
For 15 to 35 KV Load Break Elbows
•
Allows for quick and easy insertion of the probe inside the elbow
•
Prevents load break probe breakage and contamination
•
Reduces cross threading
•
Preset torque of 125 in-lb
•
Allows for quick removal by reversing the tightening action
•
Multiple drive systems:
- Adjustable T-Bar handle
-
3/8” (9.5mm) square socket drive
-
7/8” (22.2mm) hexagon for wrench
-
13/16” (20.64mm) penta
-socket wrench
OPERATING INSTRUCTIONS
Fig. 2
Fig. 3
Fig. 1
Step 1. (Fig. 2) Assemble the T-Bar handle (A) into the tool body and secure by tightening screw (B).
Step 2. Insert the probe into the tool by depressing the spring loaded lever (C), this will allow the probe to enter the tool cavity. Align
the probe hole with the tool lever pin and insert the probe until the probe hole and pin are in alignment. Release the spring loaded lever
(C) as in (Fig. 3). Be careful not to dirty or damage the arc-quenching material on the probe.
Step 3. Holding the tool with the probe locked in place, insert the probe into the load break elbow and slowly rotate the tool clockwise
to thread the probe into the crimp connector inside the elbow.
Step 4. Continue to rotate the tool and tighten until the clutch ratcheting is felt. An audible snapping will be heard, along with the
ratcheting of the tool. This will indicate the torque value of 125 in-lb has been reached.
Step 5. Depress the spring loaded lever (C) and carefully remove the tool from the probe.
TO REMOVE THE PROBE - Follow Steps 1-3; In Step 3, rotate counter-clockwise to unthread the probe.
For Additional Leverage
- The T-Bar handle can be repositioned by loosening screw (B) and sliding the T-Bar handle to the groove(s) provided.
-
A 3/8” (9.53mm) drive opening (D) at the top of the tool is also provided for using a 3/8” (9.53mm) socket wrench as leverage
.
-
7/8” (22.2mm) hexagon (E) for a fixed or adjustable wrench.
-
A 13/16” (20.64mm) pentagon (F) is provided for using a penta
-socket wrench.
Calibration
Tool torque can be checked by placing a 3/8” (9.53mm) torque wrench into the 3/8” (9.53mm) drive opening (D).
See other side for PIT 2 Instructions
(A)
(B)
PROBE
HOLE
(C)
(D)
(E)
(F)
U.S.
Patent 5,605,082
Warning! This tool is not protected against electrical shock! Always use OSHA/ANSI or other industry approved eye
protection when using tools. This tool is not to be used for purposes other than intended. Read carefully and understand
instructions before using this tool.