149
2
+(L)
3
*(M)
1
+(H)
4
Equation: 2+ (3*(1+4))
Result: 17
V1
Operator1
V2
Operator2
V3
Operator3
V4
100
-(H)
25
/(L)
2
+(M)
1
Equation: (100 – 25) / (2 + 1)
Result: 25
5.5.31 Analog math error detection
Fashion:
Classic:
Short Description
The analog math error detection block sets an output if an error has occurred in the referenced analog
math function block.
Connection
Description
Input
EN
Enable the analog math error detection function block.
Input
R
Reset the output
Parameter
Referenced FB:
block number of an analog math instruction
Error to detect:
Zero division, Overflow, or Zero division OR Overflow.
Auto Reset:
Reset the output when the failure condition clears.
Output
AQ
Q is set high if the error to detect occurred in the last execution of the
referenced analog math function block.
Parameter Referenced FB
The value for the Referenced FB parameter references the block number of an already-programmed
analog math function block.
Description of the function
The analog math error detection block sets the output when the referenced analog math function block
has an error. You can program the function to set the output on a zero division error, an overflow error,
or when either type of error occurs.
If you select the automatically reset check box, the output is reset prior to the next execution of the
function block. If not, the output retains its state until the analog math error detection block is reset with
the R parameter.
In any scan cycle, if the referenced analog math function block executes before the analog math error
detection function block, the error is detected in the same scan cycle. if the referenced analog math
Содержание ELC-12AC-R-N
Страница 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Страница 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Страница 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Страница 40: ...40...
Страница 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Страница 121: ...121 E F digital flag status F AF analog flag value...
Страница 122: ...122 G M status H AM value...
Страница 221: ...221 7 Click Install button to install Program is being installed...
Страница 247: ...247 Right click Q2 and then click Set Output State Click OK button and the Q2 of xLogic will be turned off...
Страница 250: ...250...
Страница 256: ...256 You can read the parameters from the PLC...
Страница 258: ...258...
Страница 264: ...264 Our xLogicApp Smart phone is tcp client Interface configure Modbus Poll works as TCP client...
Страница 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Страница 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Страница 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Страница 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Страница 291: ...291 Slave3 IP 192 168 0 103 TCP server port 8003 Step 2 Program in master and slave Master program...
Страница 292: ...292 B001 is used to write I1 status to F1 of slave1 the Remote 1 is the target1 in the network parameter settings...
Страница 293: ...293 B002 is used to write I1 status to F1 of slave1 the Remote 2 is the target2 in the network parameter settings...
Страница 305: ...305 Slave3 IP 192 168 0 103 UDP Server port 8003 Step 2 Program in master and slave Master program...
Страница 317: ...317 Network settings You can view the network parameters in such table...
Страница 328: ...328 Program in master You need use the MODBUS BLOCK to realize the data transmission between master and slaves...
Страница 329: ...329 B001 Transfer the I1 IA status from the master to the Q1 QA of the slave1 Setting as follows...
Страница 330: ...330 B002 Transfer the I1 IA status from the master to the Q1 QA of the slave2 Setting as follows...
Страница 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Страница 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Страница 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Страница 350: ...350 Components S1 S4 make contact Momentary switch B1 make contact Daylight control switch Circuit diagram by xLogicsoft...
Страница 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Страница 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Страница 392: ...392...