3.4
Installation premises
R
TAU N
steel boilers must be installed in a dedicated boiler
room, with adequately sized vents, in compliance with applica-
ble laws and standards.
If at all possible, the boiler should be installed on a raised base
to stop the burner fan sucking up dust and to facilitate installa-
tion of a condensate drain system.
The boiler condensate drain must be located above the height of
the lid of the system’s condensate neutraliser.
The gas supply pipe must be installed in such away that the
boiler’s panelling can be removed and the front door opened
without having to remove the burner.
9
For Belgium boilers must be installed according to the NBN
D51.003 standard, the NBN B61.001 standard (output > 70
kW).
9
When installing the boiler, allow sufficient space around it
to access all safety and control devices and to permit easy
maintenance.
9
If the specific weight of the gas supply to the burner is
greater than the specific weight of air, install all electrical
parts at least 500 mm above floor level.
0
Do not install the boiler outdoors. It is not designed to work
outdoors and is not fitted with the necessary automatic an-
ti-frost systems to do so.
≥
1,5
m
≥
L
H
≥
1m
≥
1,5
m
B
≥
1 m
L
~ 0,1
m
DESCRIPTION
TAU N
2100
2600
B - Width
1750
1850
mm
L - Length
3612
4024
mm
H - Overall height ( base)
2045
2170
mm