Technical description of the burner
4.3
Burner categories
Tab. B
4.4
Technical data
Tab. C
(1) Reference conditions: Room temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m above sea level.
(2) Pressure on the pressure switch socket (Fig. 30 at page 30) with zero pressure in the combustion chamber and at maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output.
(4) Blast tube: short-long.
4.5
Electrical data
Tab. D
Country of destination
Gas category
BE
I2E(R)
LV
I2H
CY, MT
I3B/P
BE
I3P
LU, PL
II2E3B/P
DE
II2ELL3B/P
FR
II2Er3P
AT, CH, CZ, DK, EE, FI, GR, HU, IS, IT, LT, NO, SE, SI, SK
II2H3B/P
ES, GB, IE, PT
II2H3P
NL
II2L3B/P
Model
RS 64/E MZ
Output
(1)
Max.
kW
Mcal/h
400 ÷ 850
345 ÷ 730
Min.
kW
Mcal/h
150
130
Fuel
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
Gas pressure at max. output
(2)
-
Gas: G20/G25
mbar
10.7 / 16.0
Operation
–
Intermittent (min. 1 stop in 24 hours)
–
Two progressive or modulating stages with kit (see ACCESSORIES).
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 40
Combustion air temperature
°C max
60
Noise levels
(3)
dB(A)
76
Weight
(4)
kg
42 - 44
Model
RS 64/E MZ
Main electrical supply
Control circuit power supply
3 ~ 400 / 230V +/-10% 50 Hz
1N 230V ~ +/-10% 50/60Hz
Fan motor
Hz
rpm
V
kW
A
50
2850
220/240 - 380/415
1.1
4.2/3.8 - 2.4/2.2
60
3475
254/440
1.1
3.8/2.2
Ignition transformer
V1 - V2
I1 - I2
220/240V - 1x15 kV
1 VA - 25 mA
Absorbed electrical power
kW max
1.5
Protection level
IP 40