20037075
6
GB
Technical description of the burner
3.1
Technical data
Tab. A
(*)
Firing Rate for C-ETL Canadian Listing
(1)
Reference conditions: ambient temperature 68 °F (20°C) - Barometric pressure 394” WC - Altitude 329 ft.
(2)
Pressure at test point 5)(Fig. 3) with zero pressure in the combustion chamber and maximum burner output.
(3)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
3
Technical description of the burner
Model
RS 300/EV FGR
RS 400/EV FGR
RS 500/EV FGR
Output
(1)
Delivery
(1)
max.
kW
MBtu/hr
1500 - 4220 (3834*)
5112 - 14390 (13082*)
2000 - 4995 (4541*)
6817 - 17043 (15494*)
2715 - 5740 (5217*)
9468 - 19580 (17800*)
min.
kW
MBtu/hr
555
1893
888
3030
1100
3787
Fuel
- max. delivery
- pressure at max. delivery
(2)
SCFH
“ wc
Natural gas
14070
7
Natural gas
16654
13
Natural gas
19138
15
Operation
Low - high or modulating
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °C)
Combustion air temperature
°F max
140 (60 °C)
Noise levels
(3)
dB(A)
82
85
88
Model
RS 650/EV FGR
RS 800/EV FGR
Output
(1)
Delivery
(1)
max.
kW
MBtu/hr
3300 - 7270 (6543*)
11362 - 24805 (22325*)
3885 - 8990 (8172*)
13255 - 30670 (27882*)
min.
kW
MBtu/hr
1587
5415
1330
4545
Fuel
- max. delivery
- pressure at max. delivery
(2)
SCFH
“ wc
Natural gas
24239
23
Natural gas
29973
13
Operation
Low - high or modulating
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °C)
Combustion air temperature
°F max
140 (60 °C)
Noise levels
(3)
dB(A)
90.1
88
Содержание RS 300/EV FGR