Technical description of the burner
3.8
Control box for the air/fuel ratio (LMV37.4...)
Warning notes
To avoid injury to persons, damage to property
or the environment, the following warning notes
must be observed!
The LMV37.4... is a safety device!
Do not open, interfere with or modify the unit.
Riello S.p.A. will not assume responsibility for
any damage resulting from unauthorized interfer-
ence!
³
All activities (mounting, installation and service work, etc.)
must be performed by qualified staff.
³
Before making any wiring changes in the connection area,
completely isolate the plant from mains supply (all-polar dis-
connection). Ensure that the plant cannot be inadvertently
switched on again and that it is indeed dead. If not observed,
there is a risk of electric shock hazard.
³
Ensure protection against electric shock hazard by providing
adequate protection for the burner control’s connection termi-
nals.
³
Each time work has been carried out (mounting, installation,
service work, etc.), check to ensure that wiring and parame-
ters is in an orderly state.
³
Fall or shock can adversely affect the safety functions. Such
units must not be put into operation, even if they do not
exhibit any damage.
Introduction
The control box for the air/fuel ratio (Fig. 6), (hereafter referred to
simply as the control box), that equips the burners, carries out a se-
ries of integrated functions in order to optimise burner functioning,
both for single operation and together with other units (e.g. double
furnace boiler or more than one generator at the same time).
The basic functions carried out by the control box relate to:
³
flame control;
³
the dosage of air and fuel via the positioning (with direct ser-
vocontrol) of the relative valves, excluding the possible play in
the mechanical cam calibration systems;
³
the modulation of burner output, on the basis of the load
requested by the system, maintaining the pressure or temper-
ature of the boiler at the working values set;
³
the safety diagnostic of the air and fuel circuits, via which it is
possible to easily identify any causes of malfunctioning.
Mechanical design
The following system components are integrated in the
LMV37.4... basic unit:
• Burner control with gas valve proving system
• Electronic air / fuel ratio control
• Control frequency converter air fan
• Modbus interface
Installation notes
• Always run high-voltage ignition cables separately while observ-
ing the greatest possible distance to the unit and to other cables.
• Do not mix up live and neutral conductors (fire hazard, danger-
ous failures, loss of protection against electric shock hazard,
etc.).
• Do not lay the connecting cable from the LMV37.4... to the
AZL2… together with other cables.
The first start-up, like every further operation for
the internal settings of the control box, requires ac-
cess by means of a password and is only to be car-
ried out by personnel of the Technical Assistance
Service who have been specifically trained in the
internal programming of the tool.
Electrical connection of the flame detectors
It is important to achieve practically disturbance- and loss-free
signal transmission:
• Never run the detector cable together with other cables.
– Line capacitance reduces the magnitude of the flame signal.
– Use a separate cable.
• Observe the maximum permissible detector cable lengths.
• The ionization probe is not protected against electric shock haz-
ard. It is mainspowered and must be protected against acciden-
tal contact.
• Locate the ignition electrode and the ionization probe such that
the ignition spark cannot arc over to the ionization probe (risk of
electrical overloads).
WARNING
Fig. 6
D9300
WARNING