background image

14

residence pro 32 kis

Annual Maintenance Checklist

Installer Information:

Installer Name:

Company Name: 

RIELLO Pro #:

Company Address: 

Phone Number:

Email Address:

Distributor Name:

Unit Purchase Date:    

Unit Model:

Unit Serial Number:

Installer Signature: 

Unit Commissioning:

1

p

Disconnect power supply and protect the PC board to ensure it cannot get wet during 
service

2

p

Using a digital manometer, check incoming gas pressure at the gas regulator

3

p

Using a digital manometer, check pressure at bottom of gas valve

4

p

Check gas line size & length, ensuring it is adequately sized

5

p

Isolate & drain the boiler, check  the expansion tank pressure is correct for the 
system

6

p

Check that the Pressure Relief Valve is properly oriented in a vertical position beneath 
the boiler

7

p

Check the water domestic inlet screen, clean if necessary

8

p

Check the water inlet filter screen in the inlet manifold, clean if necessary

9

p

Check the Central Heating return filter screen, clean if necessary

10

p

Check venting type, length, installation, condition & screens; clean if necessary.

11

p

Venting should be pitched towards the boiler to allow condensate to drain

12

p

Verify that the vent is not obstructed

13

p

Remove the combustion chamber cover, inspect and clean the heat exchanger, if 
necessary

14

p

Observe the condition of the rear blast board, replace if cracked or damaged

15

p

Verify spark gaps and condition of ignition electrode & flame sensor, clean or replace 
if necessary

16

p

Check the condition of the burner, ensure that it is not loose; clean if necessary

17

p

Check the boiler condensate trap, remove and clean if needed – re-prime trap

18

p

Refill the boiler and purge all air from system

19

p

Power boiler back on

20

p

Verify the polarity and ground of the power supply (L-N=120v, L-G=0v, N-G=0v)

21

p

Check incoming power to spark generator - 120 vac

22

p

Verify the unit is set for the proper gas by accessing the "Gas Type" parameter on the 
boilers front screen

23

p

Perform a combustion check per section 10.16 - Combustion Analysis in the 
Installation & Operation Instructions For Contractors using a combustion analyzer. 
Ensure the CO2% and CO ppm are within the acceptable limits given in the IOM and 
by local codes.

24

p

Ensure the CH and DHW temperature setpoints are set correctly

This document is intended 
as a guideline only. The 
Riello Installation & 
Operation Manual For 
Contractors shall be read in 
it’s entirety and adhered 
to when performing an 
annual maintenance this 
appliance. 

DANGER:  All seals, gaskets, O-rings and washers that are disturbed during maintenance must be replaced. If any 

portion of the venting system is distrubed, it must be re-installed in accordance to the vent manufacturer’s 
instructions, the Riello Installation & Operation Instructions For Contractors and any applicable provisions of 
local building codes as well as the National Fuel Gas Code ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural 
Gas and Propane Installation Code. Failure to do so may result in substantial property damage, severe injury 
or death.

WARNING: This document is intended as a guideline only, the Riello Residence PRO 32 KIS US/CAN Installation & 

Operations Instructions For Contractors must be read and followed in its entirety. Failure to do so may result 
in substantial property damage, severe personal injury or death.

Owner Information:
Name: 

ph:

Street: 

Email:   

City: 

State/Prov: 

Zip / Postal Code:

P

Please check each item after its completed, providing data as noted.

7.2  ANNUAL SERVICING CHECK LIST

Содержание Residence PRO 32 KIS

Страница 1: ...o do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your...

Страница 2: ...TIONSHIPS 10 4 13 ACCESS TO THE INFO MENU 10 4 14 LIGHTS AND FAULTS RESET PROCEDURE 10 5 HOW TO 12 5 1 HOW TO INCREASE THE SYSTEM PRESSURE 12 5 2 HOW TO SHUT DOWN THE SYSTEM FOR SHORT PERIODS 12 5 3 H...

Страница 3: ...an of the boiler WARNING There is a risk of pipes freezing if the building is left unattendedforlongperiodsoftime inexcessof12hrs infreezing temperatures In the event the building will be unoccupied f...

Страница 4: ...ivez les instructions intitul es Comment couper l admission de gaz de l appareil et appelez un technicien qualifi ou le fourmisseur de gaz pour ouvrir pour fermer 1 R glez le thermostat la temp rature...

Страница 5: ...ed in the burner flame whose information allows the control board to operate the gas valve that regulates the fuel This sophisticated control system provides the auto regulation of the combustion so t...

Страница 6: ...3 Flame sensor 14 Manual air vent hose 15 Manual upper air vent valve 16 Flue temperature sensor 17 Positive air pressure tube 18 Flue outlet 19 Air intake 20 Negative air pressure tube 21 Air pressur...

Страница 7: ...ssure is low and needs to be re pressureized Icons RESET MENU 136 F OK MODE Display SOME OF THE ICONS SHOWN ON THE CONTROL DEVICE SCREEN AT THE START UP PHASE MIGHT NOT BE AVAILABLE DURING FUNCTIONNIN...

Страница 8: ...nician or gas supplier After completing all operations required to prepare commissioning proceed as with the instructions in sections 4 6 and 4 7 sequentially to complete lighting the boiler 4 6 PROGR...

Страница 9: ...onds the value will be confirmed automatically 9 9CAUTION Adjusting your maximum heating setpoint past the design temperature of your heat emitters may cause minor injuries or property damage Consult...

Страница 10: ...mostat is set too high 4 13 ACCESS TO THE INFO MENU 9 9NOTICE Make sure you are in the Operation mode backlight ON see section 10 6 Using the boiler control panel it is possible to access the INFO men...

Страница 11: ...st purging for 45 seconds at the fan s maximum speed It is not possible to release the error before the end of the post purging unless the boiler s power supply is switched off E022 iono alarm E023 io...

Страница 12: ...maintained until the outlet water temperature reaches 131 F 55 C 9 9NOTICE The activation of the ANTI FREEZE function is indicated by the icon displayed on the front control circulator anti seize the...

Страница 13: ...technician This appliance produces carbon monoxide CO gases The venting should never be taken apart by anyone other than a qualified technician The venting should not be separated Failure to comply m...

Страница 14: ...he boiler and purge all air from system 19 p Power boiler back on 20 p Verify the polarity and ground of the power supply L N 120v L G 0v N G 0v 21 p Check incoming power to spark generator 120 vac 22...

Страница 15: ...terior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign sh...

Страница 16: ...ce accident corrosive atmospheres physical damage to the boiler alterations by unauthorized service operation contrary to the Manufactures instructions including annual cleaning or if the serial numbe...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ......

Страница 20: ...387 4663 Email info egproductsolutions com Professional Resources egproductsolutions com The Company is constantly working to perfect all of its production processes therefore the aesthetics and size...

Отзывы: