TECHNICAL ASSISTANCE

18

INITIAL START-UP

Heat is only transferred from the solar heating circuit to 
the combination storage cylinder when the temperature 
of the solar collectors exceeds that in the combination 
storage cylinder. It is therefore temperature differential 
rather than absolute temperature that is important in con-
trolling solar water heating systems.

- Set the required temperature differential between the 

collector and combination storage cylinder (see the 
instruction manual for the controller).

- Start up the boiler to provide auxiliary heating for the 

combination storage cylinder.

1

2

3

4

5

0

6

Once the system has been started up, perform the fol-
lowing checks:

Solar heating circuit

- Check that the flow rate in the solar heating circuit is 

equivalent to 30 l/h for each m

2

 of collector area

- Check that the solar heating circuit has been properly 

bled

- Check that the cold pressure of the system is approxi-

mately 3 bar

-  Check that the safety valve operates at 6 bar

-  Check that all pipes in the water circuit have been insu-

lated in conformity to relevant standards.

CHECKS DURING AND AFTER INITIAL START-UP

Содержание KOMBI 1000

Страница 1: ...cod 20145353 rev 1 05 2018 KOMBI EN INSTALLATION OPERATION AND MAINTENANCE MANUAL...

Страница 2: ...2 RANGE MODEL CODE KOMBI 800 20145308 KOMBI 1000 20145313...

Страница 3: ...l are specially trained to keep your storage cylinder efficient and cheap to run Technical Assistance Centres also stock any original spare parts that might be required This instruction manual contain...

Страница 4: ...hnical specifications 8 Accessories 9 Water circuit 10 INSTALLATION Unpacking the product page 11 Dimensions and weight 11 Handling 12 Assembly of the insulation and the lining 13 Place of installatio...

Страница 5: ...ions from the manufacturer aNever pull disconnect or twist the electrical cables coming from the appliance even if it is disconnected from the mains electricity supply The operation of any appliance t...

Страница 6: ...ITALY ACCUMULO COMBINATO PR PARATEUR SOLAIRE MIXTE M Mod le odello M N fabrication atricola C Code odice A Ann e de fabrication nno fabbricazione Capacit serpentino sanitario Capacit du serpentin san...

Страница 7: ...mperature 10 Magnesium anode 11 Flange 12 Cylinder cover 13 Flange cover 14 Domestic hot water recirculation 15 Domestic hot water outlet 16 Domestic cold water in 17 Domestic hot water probe well 18...

Страница 8: ...Flange diameter external internal 280 205 mm Probe well diameter 1 2 Coil water capacity 16 19 l Coil heat exchange surface area 2 80 3 16 m2 Power absorbed by coil 76 92 kW Continuous production of d...

Страница 9: ...GENERAL 9 COIL pressure drop PRESSURE DROP mbar FLOW RATE l h 600 700 800 900 1000 1100 500 400 300 200 100 0 0 1000 2000 3000 4000 5000 6000 Mod 1000 Mod 800...

Страница 10: ...lation instructions for the water outlet and return kit EAF Domestic cold water inlet RL DHW recirculation UAC Domestic hot water outlet MC1 Outlet from boiler 1 high temperature MC2 Outlet from boile...

Страница 11: ...lied separately from the structural work and are to be assembled upon receiving the product as described in the paragraph Assembly of the insulation and the lining The following items are delivered in...

Страница 12: ...cylinder from the pallet Place a platform of about half the height of the pallet near the storage cylinder Make sure the platform is able to support the weight of the storage cylinder Remove the brac...

Страница 13: ...hout closing completely leave one tooth open Put the washers on the attachments 4 Cut the top insulation 5 and apply it Apply the insulation 6 Close the interlocking flaps 3 completely which were prev...

Страница 14: ...ding free access to the space where the combination storage cylinder is to be installed When installing r KOMBI combination storage cylin ders in old systems or systems requiring modernisation always...

Страница 15: ...d thermostatic mixer valve Water fittings have the following specifications We recommend that you install isolating valves in the outlet and return lines MC1 Outlet from boiler 1 1 1 4 F MC2 Outlet fr...

Страница 16: ...it the domestic hot water outlet temperature b If the pressure in the solar heating circuit drops do NOT top up with water but use the proper water glycol mix Risk of freezing b All piping collectors...

Страница 17: ...boiler or hot water generator Installers must ensure proper installation and functioning in compliance with all applicable legislation It is essential to perform the following checks before starting...

Страница 18: ...er see the instruction manual for the controller Start up the boiler to provide auxiliary heating for the combination storage cylinder 1 2 3 4 5 0 6 Once the system has been started up perform the fol...

Страница 19: ...rate If the combination storage cylinder is not going to be used for an extended period of time prepare it for shut down as follows Shut down the boiler as instructed in its own manual Turn the syste...

Страница 20: ...n marks use a cloth damped in a 50 mix of water and denatured alcohol or a suitable cleaning product Dry the combination storage cylinder after cleaning it aDo not use abrasive products petrol or trie...

Страница 21: ...ting system There are problems with the storage cylinder s thermostat The pump is malfunctioning There is lime scale or sludge in the tank Water temperature is low Check the setting and condition of t...

Страница 22: ...o low Set a T of 8 10 C There is lime scale or sludge in the tank Check and clean as necessary The flow rate is too high Reduce pump speed and turn the flow rate adjustment screw on the valve group to...

Страница 23: ......

Страница 24: ...lo 7 37045 Legnago VR www riello com The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are therefore liabl...

Отзывы: