20102152

30 

GB

Start-up, calibration and operation of the burner

5.4

Adjusting gas/air delivery

Complete the procedure slowly, synchronizing the combustion with
the two servomotors and storing the different setting points.

5.5

Final calibration of the pressure switches

5.5.1

Air pressure switch

The air pressure switch is connected in differential (Fig. 37) and is
activated by both the negative pressure of the air intake and the air
pressure from the fan.
Adjust the air pressure switch (Fig. 36) after having performed all
other  burner  adjustments  with  the  air  pressure  switch  set  to  the
min. of the scale.
With the burner operating at low fire, adjust the pressure switch by
slowly turning the relative knob clockwise until the burner locks out.
Then turn the knob counter-clockwise about 20% of the set point
and start-up the burner again to ensure the set point is correct.
If the burner locks out again, turn the knob counter-clockwise a little
bit more.

DANGER

As the burner is not fitted with a device to check the
sequence of the phases, the motor rotation may be
incorrect. 
As soon as the burner starts up, go in front of the
cooling fan of the fan motor and check it is rotating
anticlockwise. See Fig. 35.
If this is not the case:

place the switch of Fig. 35 in position 

“0”

 and

wait for the control box to carry out the switch-
off phase;

disconnect  the  electrical  supply  from  the
burner;

invert the phases on the inverter output.

WARNING

For further information, please refer to the specific
instruction of the control box.

WARNING

For the start-up procedure and the parameters
calibration, refer to the specific instruction man-
ual of the LMV37... electronic cam supplied with
the burner.

DANGER

– Move slowly towards the maximum output (but-

terfly gas valve completely open);

– adjust the required maximum output with the gas

pressure stabilizer;

– adjust  the  combustion  parameters  with  the  air

servomotor and store the maximum combustion
point.

Fig. 36

D3854

Fig. 37

20048352

Содержание C9343710

Страница 1: ...20102152 3 09 2017 Installation use and maintenance instructions Forced draught gas burner Progressive two stage or modulating operation CODE MODEL C9343710 RS 120 EV BLU GB...

Страница 2: ...Original instructions...

Страница 3: ...Actuators SQM33 5 15 4 Installation 16 4 1 Notes on safety for the installation 16 4 2 Handling 16 4 3 Preliminary checks 16 4 4 Operating position 17 4 5 Preparing the boiler 17 4 5 1 Introduction 1...

Страница 4: ...5 2 Maximum gas pressure switch 31 5 5 3 Minimum gas pressure switch 31 5 6 Final checks with the burner working 31 6 Maintenance 32 6 1 Notes on safety for the maintenance 32 6 2 Maintenance program...

Страница 5: ...car ried out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shoc...

Страница 6: ...of damage to things or injury to peo ple if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreasona...

Страница 7: ...nce Only those parts envisaged by the manufacturer can be replaced 2 2 Personnel training The user is the person body or company that has acquired the ma chine and intends to use it for the specific p...

Страница 8: ...Output 1 High MBtu hr kW 2282 4924 666 1443 Low MBtu hr kW 1136 333 Fuel Natural gas Max delivery Pressure at maximum delivery 2 natural gas SCFH WC 4924 8 85 Operation Low high or modulating Standard...

Страница 9: ...on of the combustion head requires the burner to be opened and the rear part drawn back on the sliding bars The dimensions of the open burner are indicated by position I Tab E 3 6 Burner equipment The...

Страница 10: ...le 100 ft 0 36 F Example Rated Capacity 2517 MBtu hr Rated Air Pressure 1 39 WC Reference Altitude 328 ft Reference Temperature 20 C 68 F Real Altitude 3000 ft Real Temperature 17 C 62 6 F Temperature...

Страница 11: ...3 Average barometric pressure 68 F WC 399 394 385 371 358 345 332 320 307 294 1 CORRECTED BURNER AIR PRESSURE ACCORDING TO ALTITUDE Altitude Rated Pressure WC m a s l 0 100 305 610 915 1220 1525 1830...

Страница 12: ...mum furnace dimensions The firing rate was set in relation to certified test boilers Fig 4 indicates the diameter and length of the test combustion chamber Example output 2579 Mbtu hr diameter 24 inch...

Страница 13: ...an to pipe coupling 27 Switch LOCAL REMOTE 28 Gas butterfly valve 29 Boiler fixing flange 30 Flame stability disc 31 Horn 32 Button ALARM SILENCE 33 Signal POWER ON 34 Signal IGNITION ON 35 Signal FUE...

Страница 14: ...cuits via which it is possible to easily identify any causes of malfunctioning Mechanical design The following system components are integrated in the LMV37 4 basic unit Burner control with gas valve...

Страница 15: ...nal voltage Nominal current Power factor AC 120 V 50 60 Hz 1 6 A pilot duty load declaration to UL372 cos 0 4 Alarm output Nominal voltage Nominal current Power factor AC 120 V 50 60 Hz 1 A cos 0 4 Ig...

Страница 16: ...T P 10 Shutdown Operation Startup Valve proving OUTPUTS INPUTS Phase number Fuel Actuator 2 Air Actuator 1 Actuators Safety limit thermostat STB Control thermostat or pressurestat R Flame signal FS Ai...

Страница 17: ...can be seen on the dis play of the Operator Panel Index 0 for fuel actuator index 1 for air actuator Installation notes Always run the high voltage ignition cables separate from the unit and other ca...

Страница 18: ...ated in this manual and in compliance with the standards and regulations of the laws in force WARNING The handling operations for the burner can be high ly dangerous if not carried out with the greate...

Страница 19: ...nt direction compared with the oth ers With the kit this second group of tubes is substituted so that all the tubes are the same After assembling the kit check its efficiency by measuring the flue gas...

Страница 20: ...refractory lining is not necessary 11 12 Fig 12 unless expressly requested by the boiler manufacturer 4 7 Securing the burner to the boiler Detach the combustion head from the burner Fig 12 loosen th...

Страница 21: ...tion head At this point check whether the maximum delivery of the burner at high fire operation is contained in area A or in area B of the firing rate See Fig 3 at page 8 If it is in area A then no op...

Страница 22: ...ex 6 Tighten the 3 screws 1 fully down Example burner output 3750 MBtu hr If we consult diagram Fig 16 we find that for this output the ad justments are air R1 notch 2 gas R2 notch 5 Note Diagram Fig...

Страница 23: ...de the burner as far as the pipe coupling burner in the position shown in Fig 19 unscrew the 2 screws 2 from the extension 5 and reposition them as previously Fig 19 refit the screws 2 on the sliding...

Страница 24: ...bustion head within the safety time of 3s Ensure that the maximum pressure necessary for the burner is in cluded in the calibration field of the pressure regulator colour of the spring The pilot gas t...

Страница 25: ...C 5 11 1 18 3 93 WC A maximum output of 3030 MBtu hr shown diagrams corresponds to 3 93 WC pressure This value serves as a rough guide the effective delivery must be measured at the gas meter NOTE To...

Страница 26: ...ectrical supply of the burner corresponds to that shown on the identification label and in this manual Do not invert the neutral with the phase in the electrical supply line Any inversion would cause...

Страница 27: ...shown in Fig 25 Key Fig 25 1 Motor supply cable 2 Single phase supply cable 3 Connecting cable between the inverter and the electronic cam WARNING It is very important to shield the motor cable 1 as...

Страница 28: ...the case of clamp type B pull the indicated tabs upwards and lift until locked in the open position B1 Fig 26 insert the shielded cable with the shielding inside the clamp B2 put pressure on the indic...

Страница 29: ...lamping the cable to the earth plate The screen must be earthed on both side of the cable take care for good earthing system Examples Number 1 2 3 show not proper ways to earth a cable screen WARNING...

Страница 30: ...ors manufactured for 208 230 460 IE3 NEMA Premium Efficiency voltage have the same connection than IE2 Epact motors but differ ent connection than IE1 motors no more star delta but star double star D3...

Страница 31: ...ssure switches set the parameters on the RWF55 regulator Please refer to the specific manual for this operation Turn the switch of Fig 35 to position ON and turn the switch of Fig 35 to position LOCAL...

Страница 32: ...burner locks out again turn the knob counter clockwise a little bit more DANGER As the burner is not fitted with a device to check the sequence of the phases the motor rotation may be incorrect As so...

Страница 33: ...r operating at MAX output increase adjustment pressure by slowly turning the relative dial clockwise until the burn er locks out Then turn the dial anti clockwise by 0 8 WC and repeat burner starting...

Страница 34: ...h the UV scanner Fig 40 proceed as follows extract the UV scanner 2 clean the glass cover from any dust that may have accumu lated Fan Check to make sure that no dust has accumulated inside the fan or...

Страница 35: ...comply with the regulations in force or at any rate do not produce good combustion Use the appropriate card to record the new combustion values they will be useful for subsequent controls 6 3 Flame si...

Страница 36: ...der to close the burner re install all components with reverse procedure remove the 2 extensions 9 and re screw the screws 8 on the sliding bars 4 push the burner up to approximately 4 from the pipe c...

Страница 37: ...ndix Spare parts 31 34 10 1 2 3 4 6 21 27 26 52 50 28 52 52 54 60 35 46 30 37 33 39 38 36 53 69 55 58 56 70 62 50 32 32 5 23 13 23 25 12 51 40 14 19 47 48 16 59 8 7 17 44 48 22 18 20 49 9 47 48 57 43...

Страница 38: ...BLY C 21 20030200 MOTOR 2 2 KW C 22 3014106 FUSE 6 3A A 23 20036017 GREEN SIGNAL LIGHT C 24 20042704 SPEED SENSOR 25 20027014 WHITE SIGNAL LIGHT C 26 3013681 SCREW C 27 3003891 CONNECTOR C 28 3014079...

Страница 39: ...extended safety fittings 52 3013937 HUB 53 301249 SCREW 54 3012639 CONTROL DEVICE 55 20030203 SHUTTER C 55 20030202 SHUTTER C 56 20030204 BRACKET 57 20086579 UV PHOTOCELL A 58 20030206 END CONE 59 302...

Страница 40: ...Tubes kit Gas train according to UL Standards B Appendix Accessories Burner Code RS 120 EV BLU 3010248 WARNING The installer is responsible for the supply and instal lation of any required safety dev...

Страница 41: ...2 Low Fire High Fire Main Power Supply O2 Low Fire High Fire Control Power Supply CO Low Fire High Fire Burner Firing Rate NOX Low Fire High Fire Manifold Pressure Net Stack Temp Low Fire High Fire Pi...

Страница 42: ......

Страница 43: ......

Страница 44: ...URNERS NORTH AMERICA 35 Pond Park Road http www riello ca 2165 Meadowpine Blvd Hingham Massachusetts Mississauga Ontario U S A 02043 1 800 4 RIELLO Canada L5N 6H6 RIELLO S p A I 37045 Legnago VR Tel 3...

Отзывы: