GB
TEST BOILER
The working field has been defined according to EN 676 standard.
COMMERCIAL BOILERS
The burner-boiler matching is assured if the boiler conforms to EN 303 and the combustion chamber dimensions
are similar to those shown in the diagram EN 676. For applications where the boiler does not conform to EN 303,
or where the combustion chamber is much smaller than the dimensions given in EN 676, please consult the
manufacturers.
CORRELATION BETWEEN GAS PRESSURE AND BURNER OUTPUT
To obtain the maximum output, a gas head pressure of 5.8 mbar is measured (
M2
, see chapter 3.3, page 4) with
the combustion chamber at 0 mbar using gas G20 with a net heat value of 10 kWh/Nm
3
(8,570 kcal/Nm
3
).
3.
INSTALLATION
THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS.
3.1
BOILER FIXING
4
1
2
3
5
6
7
Gas pressure in
the
co
mb
ust
ion hea
d
– mbar
40,000
50,000
60,000
70,000
kcal/h
120
60
50
70
80
kW
Thermal power
D5257
110
80,000
90
100
90,000
40
100,000
S7392
HINGE
ASSEMBLY
1
3
2
A
B
D5108
Boiler door must have a max. thickness of
90 mm
,
refractory lining included.
If thickness is greater
(max. 150 mm)
, a combustion
head extension must be fitted, which is supplied
separately.
IMPORTANT
O
Separate the combustion-head assembly
from the burner body by removing nut (1) and
removing group
(A)
.
O
Fix the head assembly group
(B)
to the boiler
(2) insert the supplied insulating gasket (3).