
19
20171652
GB
Installation
4.9
FGR duct system
–
Normally the duct would connect to the stack as shown in
Fig. 18, with a 45° cut facing the flue gas flow and with the
center of the cut centered in the stack.
The duct could be made to the smoke box, but must still be
located with the same 45° cut facing the flue gas flow stream
and with the center of the cut in the center of the stream.
–
The duct should be routed in a manner that has the minimum
number of elbows and provides for the normal expansion and
contraction of the piping.
Long duct runs can change length by over 1” and can put an
extreme load on the connecting points that could cause com-
ponent failures.
The design must include offsets that will allow for the required
movement of the piping without undue force on the burner or
stack.
–
Duct expansion and contraction can be managed by using
two relatively long duct runs that are 90° apposed to each
other.
A small movement in the angle between these two legs will
provide the space needed to absorb the expansion and con-
traction. The ends of the FGR duct must be securely attached
to allow this to work properly, and prevent high loads from be-
ing applied to the burner or stack.
–
A condensation drip leg must be provided upstream of the
FGR control valve and the FGR shutoff valve (if used).
There must be sufficient condensate drip legs and catch
space (volume of drip legs) to prevent the condensation from
flowing through the control valves and into the fan. In cases
of heavy condensation, a condensate drip leg may be re-
quired on the bottom of the housing, to remove condensate.
–
Determine if pipe reducers are needed for the connection to
the FGR control valve and the FGR shutoff valve.
–
The duct must be properly supported, handling both the
weight of the duct and to control the thermal expansion and
contraction. The supports may need to be anchored to pro-
vide this stability in the FGR duct.
–
The FGR duct is normally made from schedule DN65 pipe.
–
The duct components must be seal welded, flanged or
screwed together to provide an air tight duct.
Air leakage into the duct will prevent the system from working
properly. It is sufficient to only inspect the welds for a proper
seal, they do not need to be leak tested.
Burner
2
Inducted FGR modulating damper
3
Flue gas recirculation pipe
4
Boiler stack
5
Alternate construction using “T”
6
Flue pressure intake upstream of damper 2)
7
Boiler
8
Drain valve (manual ball valve, stainless steel)
9
Drain line
10 Condensate trap
11 Primary gas supply inlet
CAUTION
Uncontrolled condensation can cause premature
failure of the control valves, fan and motor.
Adequate means must be provided to remove
condensation from the system.
Cold startup will generate significant amounts of
condensation.
WARNING
The duct and connectors must be duly insulated to
prevent accidental burns.
45
3
10
5
8
8
2
9
8
4
6
3
7
1
11
Fig. 18
20186189
Содержание 20171510
Страница 2: ...Original instructions...
Страница 51: ...49 20171652 GB Appendix Electrical panel layout 0 1 1 1 1 2 3 4 3 3 4 3 5 2 6 6 6 7 6 8 6 6 6 6 6 6 6 6 6 6 7 6...
Страница 52: ...20171652 50 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01...
Страница 53: ...51 20171652 GB Appendix Electrical panel layout...
Страница 54: ...20171652 52 GB Appendix Electrical panel layout 0 1 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2...
Страница 55: ...53 20171652 GB Appendix Electrical panel layout 0 0 0 12 3456 7 12 3456 7...
Страница 56: ...20171652 54 GB Appendix Electrical panel layout 01 2 30 3 1 2 0 40 20 22 2 3 5 636 078 40 9 025 7 5...