Technical description of the burner
4.16 Calibration of the thermal relay
The thermal relay serves to avoid damage to the motor due to an
excessive absorption increase or if a phase is missing.
For calibration 2), see the table in the wiring diagram.
To reset, in case of an intervention of the thermal relay, press the
"RESET" button 1) of Fig. 10.
The red “TEST” button 3) opens the NC (95-96) contact and
stops the motor.
CAUTION
The automatic reset (Position “A” button 1) can be
dangerous. This operation is not anticipated in the
burner's operation, leave it always on “H”.
Therefore do not position the “RESET” button
1) on “A”.
Fig. 10
20073932
3
1
2
RESE
T
H
A
TEST
95
96
97
98
Содержание 1135T1
Страница 2: ...Translation of the original instructions...
Страница 29: ...27 20173117 GB Installation Fig 20 No Setpoint air gas Max burner output kW 20081480...
Страница 53: ...51 20169327 GB Appendix Electrical panel layout ALL MODELS RS 310 RS 410 DIRECT START UP...
Страница 54: ...20169327 52 GB Appendix Electrical panel layout RS 310 RS 610 STAR TRIANGLE START UP...
Страница 57: ...55 20169327 GB Appendix Electrical panel layout ALL MODELS...
Страница 58: ...20169327 56 GB Appendix Electrical panel layout ALL MODELS...
Страница 59: ...57 20169327 GB Appendix Electrical panel layout 0 ALL MODELS...
Страница 60: ...20169327 58 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ALL MODELS...
Страница 61: ...59 20169327 GB Appendix Electrical panel layout 0 1 1 1 2 ALL MODELS...
Страница 66: ...20169327 64 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3 ALL MODELS...