FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
EnergyShare
Select the auxiliary socket
operating mode
Always
connected
Always connected
Disconnection after no. seconds of battery
operation
Disconnection after no. seconds of the battery
discharge pre-alarm signal
... (see
UPStools
manual)
Bypass voltage
thresholds
Selects
the
permitted
voltage range for switching
to the bypass
Low:
180V
High: 264V
Low: 180 - 200 in 1V steps
High: 250 - 264 in 1V steps
Bypass
voltage
threshold for ECO
Selects
the
permitted
voltage range for operation
in ECO mode
Low:
200V
High: 253V
Low: 180 - 220 in 1V steps
High: 240 - 264 in 1V steps
Intervention
sensitivity for
ECO
Selects the intervention
sensitivity during operation
in ECO mode
Normal
Low
Normal
High
Power-on delay
Waiting time for automatic
switching back on after
mains power returns
5 sec.
Disabled
(1 - 255) sec. in 1 sec steps
Remote power-
on/off function
Selects
the
function
associated with the RS232
connector.
Disabled
Disabled
Remote ON
Remote OFF
Remote ON/OFF
Input
configuration
three-phase /
Single-phase**
Selects the Input mains type Three-phase
Three-phase
Single-phase
** Only for versions SPH 8 - 10 - 10 ER - 15 - 20 - 20 ER. For further information about mains connections, please refer
to the relative chapter “Connections”