Erstellt/
Prepared by
:
CRQ/AL
am/
on
:
27.01.11
Seite/
Page
:
1
QM-Nr./
QM-No.
:
0905-40-1049_NK/4-00
Genehmigt/
Released by
:
CRQ/AL
am/
on
:
27.01.11
von/
of
:
1
A Unit of IDEX Corporation
Kempen, 27.01.2011
SIL
Declaration by the Manufacturer
Functional Safety according to IEC 61508
We declare, that the devices
NK, NKS, NKL
are suitable for use in a safety related application, if the safety instructions and the following
parameters are observed:
Device Type:
A
Proof Test Interval:
≤ 1 year
HFT:
0 (single channel usage)
λ
SU
:
231 FIT
λ
SD
:
26 FIT
λ
DU
:
195 FIT
λ
DD
:
62 FIT
SFF:
62,1 %
PFD
Avg
:
8,54 10
-4
(for T
Proof
= 1 year)
MTBF:
222 years
Safety Integrity Level:
SIL 2
The specified values are valid only for the valve. Accessories such as an actuator, solenoid
valves, limit switches etc. are not included.
______________________________
______________________________
Gregor Kleining
Alexander Linges
Dir. Research & Development
Quality Manager