86
920i
Installation Manual
Format Identifier
Defined By
Description
<P[G | N | T]>
STR.POS#
n
STR.NEG#
n
Polarity. Specifies positive or negative polarity for the current or
specified (Gross/Net/Tare) weight on the source scale.
<U[P | S | T]>
STR.PRI#
n
STR.SEC#
n
STR.TER#
n
Units. Specifies primary, secondary, or tertiary units for the current or
specified weight on the source scale.
<M[G | N | T]>
STR.GROSS#
n
STR.NET#
n
STR.TARE#
n
Mode. Specifies gross, net, or tare weight for the current or
specified weight on the source scale.
<S>
STR.MOTION#
n
STR.RANGE#
n
STR.OK#
n
STR.INVALID#
n
Status for the source scale. Default values and meanings for each
status:
STR.MOTION#
n
M
In motion
STR.RANGE#
n
O
Out of range
STR.OK#
n
<space>
OK
STR.INVALID#
n
I
Invalid
<B [–]n,…]
See descriptions below
Bit fields. Comma-separated sequence of bit field specifiers. Must
not exceed 8 bits.
B0
—
Always 0
B1
—
Always 1
B2
Configuration
=1 if even parity
B3
Dynamic
=1 if MODE=NET
B4
Dynamic
=1 if COZ
B5
Dynamic
=1 if standstill
B6
Dynamic
=1 if gross negative
B7
Dynamic
=1 if out of range
B8
Dynamic
=1 if secondary/tertiary
B9
Dynamic
=1 if tare in system
B10
Dynamic
=1 if tare is keyed
B11
Dynamic
=00 if MODE=GROSS
=01 if MODE=NET
=10 if MODE=TARE
=11 (
not used
)
B12
Dynamic
=00 if UNITS=PRIMARY
=01 if UNITS=SECONDARY
=10 if UNITS=TERTIARY
=11 (
not used
)
B13
Configuration
=00 (
not used
)
=01 if current DSPDIV=1
=10 if current DSPDIV=2
=11 if current DSPDIV=5
B14
Configuration
=00 (
not used
)
=01 if primary DSPDIV=1
=10 if primary DSPDIV=2
=11 if primary DSPDIV=5
B15
Configuration
=00 (
not used
)
=01 if secondary DSPDIV=1
=10 if secondary DSPDIV=2
=11 if secondary DSPDIV=5
Table 10-6. Custom Stream Format IdentiÞers