Configuration
35
3.2.7
Analog Output Menu
The ALGOUT menu is shown only if the analog output option is installed. If the analog output option is
installed, conÞgure all other indicator functions and calibrate the indicator itself before conÞguring the analog
o u t p u t
Figure 3-12. Analog Output Menu
3.2.8
Version Menu
The VERS menu can be used to check the installed software version or, by using the
Reset Config
softkey, to
restore all conÞguration parameters to their factory default values. There are no parameters associated with the
Version menu: when selected, the indicator displays the installed software version number.
Figure 3-13. Version Menu
ALG OUT Menu
Parameter
Choices
Description
Level 2 submenus
SOURCE1
PROG
SCALE
n
Specifies the scale tracked by the analog output. PROG indicates that the analog output is under
program control.
MODE1
GROSS
NET
Specifies the weight data, gross or net, tracked by the analog output.
OFFSET
0%
20%
Zero offset. Select 0% for 0–10 V or 0–20 mA output; select 20% for 4–20 mA output. This
parameter must be set before calibrating the analog output.
ERRACT
FULLSC
HOLD
ZEROSC
Error action. Specifies how the analog output responds to system error conditions.
Possible values are:
FULLSC: Set to full value (10 V or 20 mA)
HOLD: Hold current value
ZEROSC: Set to zero value (0 V or 4 mA)
MIN
000000
0–9999999
Specifies the minimum weight value tracked by the analog output. Specify a value in the range
0–9999999.
MAX
010000
0–9999999
Specifies the maximum weight value tracked by the analog output. Specify a value in the range
0–9999999
TWZERO
40
0–65535
Tweak zero. Enter tweak value to adjust the analog output zero calibration. Use a multimeter to
monitor the analog output value.
TWSPAN
59650
0-65535
Tweak span. Enter tweak value to adjust the analog output span calibration. Use a multimeter to
monitor the analog output value.
Table 3-8. Analog Output Menu Parameters
SCALES
SERIAL
FEATURE
PFORMT
SETPTS
DIG I/O
ALGOUT
VERS
number
40
number
SOURCE1
PROG
OFFSET
20%
0%
ERRACT
SCALE
n
FULLSC
HOLD
ZEROSC
MIN
number
000000
MAX
number
10000
TWZERO
59650
TWSPAN
MODE1
GROSS
NET
If SOURCE1
¹
PROG
SCALES
SERIAL
FEATURE
PFORMT
SETPTS
DIG I/O
ALGOUT
VERS
Software
version