HEATER
for
KS
cod.ACQ9092 (230V 50-60Hz) - cod.ACQ9093 (120V 60Hz)
The motor HEATER card is used in cold countries to avoid the block for cold of the motor.
This card activate itself automatically with gate completely closed with 0°C temperature (detected
with the thermal PROBE).
When the motor is moving, or stopped with gate open, the HEATER is not active.
Only after 5 seconds that the gate has completely closed, the HEATER turn on (only if the external
temperature is below -0°C).
HOW TO FIX THE CARD
Insert the plastic connectors into the holes of the metallic plate (inside the KS plastic container) or
into the holes of the plastic support (inside the K series operators), than insert the heater card on
them.
SET THE CARD WITH THE RIGHT OPERATOR
Setting jumper JP1 and JP2 you will set the card to operate to the right operator as described on
the chart here below.
CONNECTIONS
1. Turn off the power.
2. Remove the protection on plug J17 of KS control panel.
3. Connect the power cableto the plugs N-L of the heater card and insert the female terminal into
the connector J17.
4. Connect the signal cable into connectors J16 (3 poles) of the control panel KS and J3
(2 poles) of the HEATER card.
5. Execute the connections between motor and heater card as described in the picture.
6. The thermal PROBE must be connected only at the end of the adjustment.
IMPORTANT: Don’t remove the capacitor from KS connectors.
ADJUSTMENT OF THE HEATING VOLTAGE
To execute the adjustment you have to use a multimeter (tester) setted on Vac with a limit
of almost 300Vac.
1. Verify which the thermal PROBE is not connected. This to execute the adjustment of th
e HEATER card also with temperature over -0°C.
2. Rotate the trimmer at the minimum value (anti-clockwise sense).
3. Turn on the power. After 5 seconds the relay on the heater card will be active.
4. Connect the multimeter to the plugs V-OUT and U-OUT of the HEATER CARD to read the
voltage. Rotate trimmer searching the correct voltage value for the motor you have installed
following the table here below.
WARNING!
At the and of the adjustment, connect the thermal PROBE.
Put the probe near the motor as described here below:
If heater card is installed inside the opertator, on a side of KS, it is possible to reduce the PROBE
cable (min 25÷30 cm). Put the PROBE down near the base of the operator.
If heater card is installed outsode the operator, put the probe ina a way which can detect the ouside
temperature.
TECHNICAL FEATURES
Temperature range
0÷±55°C
Umidity
<95% without condensation
Power Supply
230Vac 50-60 Hz (cod.ACQ9092)
Power Supply
120Vac 60 Hz (cod.ACQ9093)
Current without charge
12mA
Weight 0,25
Kg
Dimensions
117x58x35 mm
K800-K1400
K2200
KING
Jumper JP1
Jumper JP2
Temperatures
trimmer min.
20V - 360 mA
18V - 570 mA
20V - 250mA
- 0 °C ÷ - 5 °C
trimmer mid.
24V - 400 mA
21V - 630 mA
22V - 270 mA
- 5 °C ÷ - 10 °C
trimmer max.
60V - 1,58 A
34V - 1,43 A
61V - 1,20A
> - 10 °C
25014 CASTENEDOLO (BS)-ITALY
Via Matteotti, 162
Te+39.030.2135811
T+39.030.21358279-21358278
http://www.ribind.it - email: [email protected]
automatismi per cancelli
automatic entry systems
®
FOR 120V-60Hz OPERATORS
K800-K1400
K1800
K2200
SUPER 2200
KING
Jumper JP1
Jumper JP2
Temperatures
trimmer min.
52V - 200 mA
27V - 220 mA
30V - 300 mA
26V - 250mA
72V - 200mA
- 0 °C ÷ - 5 °C
trimmer mid.
58V - 240 mA
36V - 310 mA
40V - 380 mA
31V - 310mA
80V - 230mA
- 5 °C ÷ - 10 °C
trimmer max.
116V - 600 mA
115V - 1,4 A
115V - 1,5 A
112V - 1,50A
150V - 580mA
> - 10 °C
FOR 230V-50/60Hz OPERATORS