32
Once the network voltage is back, the recharge card starts charging the
battery and the battery state led switches off. It is sufficient to press the
remote control (or the OPEN 1 or OPEN 2 or the START command) to open
the barrier. When the barrier is open, give a CLOSE command or wait the
pause time before the automatic closing => the barrier starts closing.
When closed, the normal operations are reactivated.
DIP 9 - ON =>
with black out the barrier opens automatically. Batteries state led turns on
and all controls are disabled. When the power supply is back, the barrier
closes immediately thus resetting the controls and safeties operations.
IN CASE NO BATTERY IS CONNECTED
, through the DIP 10 you can have the following
options:
DIP 10 - OFF =>
With black out the barrier stays still or, in case it is moving, it stops. Once
the power supply is back, it is sufficient to press the remote control, OPEN
1, OPEN 2 or START commands to open the barrier. When the barrier is
open, give a CLOSE command or wait the pause time before the automatic
closing => The barrier starts closing => When closed, the normal
operations are reactivated. During the realignment the safeties are active.
DIP 10 - ON =>
At the return of the power supply the barrier closes if it was open. It doesn’t
close only in case the clock feature is active. (see B.I.O. command).
OPERATING SAFETY ACCESSORIES
SECURITY LOCK
For a correct functioning of the system, the DL5 led must always be on to signal that the
manual release has not been activated. If the DL5 led is off no movement of the barrier is
allowed because it has been manually released with the special key.
ENCODER
It has the duty to act as security and to define the running, both during the closing and the
opening phase, with reversal of the movement.
It is possible to exclude the ENCODER, which only functions as security, through DIP 7 (OFF).
In case the ENCODER should not work (not fed, disconnected wires or faulty) the movement
of the barrier is not carried out.
If after a first intervention of the ENCODER in closing or opening phase there is a second
one, obviously in the contrary sense, the barrier stops and then reverses for 1 sec. The bell
(buzzer optional) will be activated to signal the alarm state for 5 minutes and the flashlight
will be active for a minute.
During or after the 5 minutes of sounding alarm (buzzer optional), it is possible to reset the
functioning of the barrier by pressing any control button.
PHOTOCELL (COM A+/PHOT 1/PHOT 2) - Safety function PL “b” according to EN13849-
1
If an obstacle is placed in range of the photocells when the barrier is closed and the command
to open is given, the barrier opens (the photocells do not work while opening). Photocells
work only during closing (with reverse motion restored after a second, even if they are still
engaged).
When the photocell is activated, the buzzer emits 1 tone.
ATTENTION: In case the receiver led remains lit, malfunctioning of the main supply
is suspected.
It is advisable to connect electrically to earth the columns
or the photocells stands to the terminal D-, to shield the
photocells from external noise.
Be careful not to short circuit the system when the supply
phases are inverted!
PHOTOCELL MONITORING (A+ TEST/A-)
Connect the photocell transmitter to A + TEST / A- and set DIP 7 to ON.
Monitoring consists of a Functional Test of the photocell, performed before each maneuver.
The barrier maneuver is therefore only permitted if the safety (s) have passed the Functional
Test.
Attention:
monitoring of the photocell input can be enabled with DIP 7 in ON, or disabled
with DIP 7 in OFF.
WARNING: If the AUTOTEST feature is enabled and only one photocell is connected,
a jumper must be made between the PHOT 1 and PHOT 2 terminals. If
the jumper is not made, the AUTOTEST fails and the gate will not move.
ALARM AUTOTEST PHOTOCELLS FAILED (DIP 7 ON)
At each command, if the photocell monitoring fails, an alarm is triggered by the buzzer which
emits 4 tones every 5 seconds. In this condition the barrier remains firm. Only by repairing the
photocell and pressing one of the enabled commands, operation can be restored.
SAFETY EDGE (COM A+/EDGE) - Safety function PL “b” according to EN13849-1
During closing, if Safety edge is pressed, it reverses the opening motion. If the safety edge
remains busy, it does not allow closure.
If the safety edge is not installed, jump the COM A+/EDGE terminals.
SAFETY EDGE ALARM
The flasher and the buzzer are activated with 2 tones every 5 seconds for one minute.
STOP BUTTON (COM A+/STOP) - Safety function PL “b” according to EN13849-1
During the movement of the barrier the STOP button stops it.
If the STOP button is pressed fully open (or partially using the pedestrian control), automatic
closing will be temporarily disabled (if enabled by TCA trimmer with DL9 LED on). It will
therefore be necessary to give a new command to close the barrier.
The automatic closing will be reactivated when the barrier has closed again (if it was enabled
by TCA trimmer with DL9 LED on).
STOP BUTTON (COM A+/STOP) - Safety function PL “b” according to EN13849-1
During the movement of the barrier the STOP button stops it.
If the STOP button is pressed fully open, automatic closing will be temporarily disabled (if
enabled by TCA trimmer with DL9 LED on). It will therefore be necessary to give a new
command to close the barrier.
Automatic closing will be reactivated when the barrier has closed (if it was enabled by TCA
trimmer with LED DL9 on).
HOLD-TO-RUN COMMAND OPERATION (with command maintained) IN CASE OF
FAILURE OF THE SAFETY DEVICES
If the edge is broken or engaged for more than 5 seconds, or if the photocell is faulty or
engaged for more than 60 seconds, the OPEN 1, OPEN 2, CLOSE and START commands will
only operate with maintained command.
The activation signaling of this operation is given by the DL1 led that flashes.
This operation allows opening or closing only by keeping the control buttons pressed. The
radio command and automatic closing are excluded because their operation is not permitted
by the standards.
When the safety contacts are reset, the automatic or step-by-step operation is automatically
re-enabled after 1 second, and therefore the radio control and automatic closing are resumed.
Note 1: during this operation in the event of a coast fault (or photocells) the photocells (or
edge) still operate interrupting the maneuver in progress.
Note 2: the STOP button is not considered a safety to be bypassed in this mode, so if it is
pressed or broken, it does not allow any maneuver.
The maneuver with maintained command is exclusively an emergency maneuver that
must be carried out for short periods and with the visual safety of the automatism
movement. Faulty protections must be restored as soon as possible for correct
operation.
VISUAL AND SOUND ALARMS
FLASHER
IMPORTANT: This electronic panel can power only one flasher with flashing circuit (ACG7061)
with a 24V and 20W (maximum) lamp.
If you exceed 20W, the electronic
panel’s logic will be compromised, with the system possibly stopping.
BUZZER
It has the task of signaling the intervention of the safety devices, the status of the alarms and
the state of memorization and cancellation of radio codes.
GATE OPEN 24Vdc INDICATOR LIGHT (COM A+/SIGNAL -)
The light signals that the gate is open, partly open or not completely closed. Only when the
gate is completely closed does the light turn off.
During opening, it flashes slowly.
When the gate is stationary or opened, it is permanently on.
During closing, it flashes quickly
If the mains voltage is missing and the emergency batteries are activated, this warning light
comes on to signal the lack of mains, and starts flashing (2 flashes 250 ms on-off followed
by a pause of 2 seconds) only when the batteries are empty.
When the light flashes continuously 500 ms on-off, the control unit is no longer operational.
Only when the mains voltage returns, the warning light goes out and all the controls are reset
(obviously the batteries will be recharged only in the presence of mains voltage).
N.B.: Max 3 W. If warning lights are in excess, the control panel processes will be
endangered with possible stop of all operations.
TECHNICAL CHARACTERISTICS
- Humidity
< 95% without condensation
- Feeding tension
230V~ ±10%
24Vdc
Cont.
10
G