Rheem RXRF-FBB1 Скачать руководство пользователя страница 1

OUTSIDE AIR

ASSEMBLY

ADJUSTABLE SLIDE DAMPER

2-POSITION MOTOR

SUPPLY DUCT

COVER

A/C UNIT

RETURN DUCT COVER (REMOVED)

The 0-35% manual outside air system is designed to replace the unit duct cover.  No drilling on the unit or field assembly is
required.  A 2-position control motor opens the intake damper when the blower is energized.  The amount of air is
controlled by the a slide damper on damper motor.  The intake panel is fully insulated..

STEP 1:
Check for correct number of parts.  See list below:

1 ea. - Outside Air Intake damper assembly with hood and slide damper.

STEP 2:
Remove return air duct cover from unit, and save the screws.

STEP 3:
Remove filter access panel. Plug the “PL5" connector to ”PL2" connector in return section.

STEP 4:
Install outside air assembly as shown in Figure 1 over duct opening with the screws removed in Step 2.

STEP 5:
Adjust the slide damper to the desired position.

FIGURE 1

INSTALLATION INSTRUCTIONS

MODEL RXRF - FBB1

0-35% MOTORIZED OUTSIDE AIR

MARCH 2, 1998

RM35MAD20B

OUTSIDE AIR HOOD