1. Specifications

Type

Inverter heat pump

Model name

ROSH18AXFWJ

ROSH24AXFWJ

Power supply

208/230 V ~ 60 Hz

Available voltage range

187—253 V

Starting current

A

8.0

10.5

Fan

Airflow rate

Cooling

CFM (m

3

/h)

1,489 (2,530)

2,001 (3,400)

Heating

1,489 (2,530)

2,119 (3,600)

Type × Q'ty

Propeller fan × 1

Motor output

W

100

Sound pressure level *1

Cooling

dB (A)

47

54

Heating

50

55

Heat exchanger type

Dimensions
(H × W × D)

in

31-7/16 × 35-7/16 × 1-7/16

mm

798 × 900 × 36.4

Fin pitch

FPI

20

Rows × Stages

2 × 38

Pipe type

Copper

Fin type

Type (Material)

Corrugate (Aluminum)

Surface treatment

Corrosion resistance (Blue fin)

Compressor

Type × Q'ty

Hermetic motor compressor × 1

Motor output

W

2,100

Refrigerant

Type

R410A

Charge

lb oz

4 lb 10.1 oz

g

2,100

Refrigerant oil

Type

POE (RB68)

Amount

in

3

 (cm

3

)

48.8 (800)

Enclosure

Material

Steel sheet

Color

Beige

Approximate color of MUNSELL 10YR7.5/1.0

Dimensions
(H × W × D)

Net

in

32-11/16 × 35-7/16 × 13

mm

830 × 900 × 330

Gross

in

39-3/8 × 41-5/16 × 17-1/2

mm

1,000 × 1,050 × 445

Weight

Net

lb (kg)

135 (61)

Gross

152 (69)

Connection pipe

Size

Liquid

in (mm)

Ø 3/8 (Ø 9.52)

Gas

Ø 5/8 (Ø 15.88)

Method

Flare

Pre-charge length

ft (m)

66 (20)

Max. length

164 (50)

Max. height difference

98 (30)

Operation range

Cooling

°F (°C)

-5 to 115 (-20 to 46)

Heating

-5 to 75 (-20 to 24)

Drain hose

Material

LDPE

Size

mm

Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)

NOTES:

• Specifications are based on the following conditions:

– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB).
– Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)

• Protective function might work when using it outside the operation range.
• *1: Sound pressure level

– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.

DESIGN & TECHNICAL MANUAL

- 32 -

OUTDOOR UNIT

ROSH18-24AXFWJ

Содержание RIWH18AVFJ

Страница 1: ...AIR CONDITIONER Wall mounted type REFRIGERANT R410A INVERTER DESIGN TECHNICAL MANUAL INDOOR RIWH18AVFJ RIWH24AVFJ OUTDOOR ROSH18AXFWJ ROSH24AXFWJ DR_AS043EM_01 2017 01 27...

Страница 2: ...Notices Product specifications and design are subject to change without notice for future improvement For further details please check with our authorized dealer...

Страница 3: ...ns 9 5 2 Airflow 12 6 Operation noise sound pressure 14 6 1 Noise level curve 14 6 2 Sound level check point 15 7 Safety devices 16 8 External input and output 17 8 1 External input 17 8 2 External ou...

Страница 4: ...8AXFWJ 38 5 2 Model ROSH24AXFWJ 39 6 Capacity compensation rate for pipe length and height difference 40 6 1 Models ROSH18AXFWJ and ROSH24AXFWJ 40 7 Additional charge calculation 41 7 1 Models ROSH18A...

Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE RIWH18AVFJ RIWH24AVFJ...

Страница 6: ...ons H W D in mm Main 14 7 8 32 3 4 1 1 16 378 832 26 6 Sub 3 5 16 32 3 4 1 2 84 832 13 3 Fin pitch FPI Main 21 Sub 18 Rows Stages Main 2 18 Sub 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Ma...

Страница 7: ...8 12 5 8 320 39 5 16 998 Outline of unit 18 9 16 471 2 5 8 67 1 1 8 28 1 13 16 46 17 1 4 438 2 3 8 61 4 102 15 5 8 397 17 432 2 3 16 56 2 3 16 56 3 8 10 12 5 8 320 11 16 17 3 1 8 80 hole Piping inlet...

Страница 8: ...nt Provide sufficient installation space for product safety Unit in mm 3 63 or more 4 80 or more 3 52 or more 3 53 or more 4 80 or more Outline of unit 5 120 or more 60 1 500 or more 71 1 800 or more...

Страница 9: ...3 Wiring diagrams 3 1 Models RIWH18AVFJ and RIWH24AVFJ 5 WALL MOUNTED RIWH18 24AVFJ...

Страница 10: ...21 43 12 83 1 26 95 14 23 9 86 1 30 15 87 9 93 1 32 17 47 10 82 1 34 18 02 11 67 1 35 19 11 11 63 1 36 20 16 12 39 1 38 104 13 58 9 59 1 45 15 12 9 66 1 47 16 65 10 54 1 49 17 16 11 36 1 50 18 22 11...

Страница 11: ...11 50 1 92 20 54 12 42 1 93 21 77 12 35 1 95 23 00 13 17 1 97 115 12 35 9 21 1 56 13 75 9 28 1 58 15 18 10 13 1 61 15 63 10 92 1 61 16 58 10 88 1 63 17 50 11 60 1 65 AFR m3 h 1 120 Indoor temperature...

Страница 12: ...2 97 8 43 3 03 8 22 3 09 15 0 10 0 8 57 2 48 8 37 2 53 8 16 2 58 7 96 2 63 7 75 2 68 Model RIWH24AVFJ AFR CFM 677 Indoor temperature FDB 60 65 70 72 75 Outdoor temperature FDB FWB TC IP TC IP TC IP T...

Страница 13: ...7 8 ft 7 14 20 27 7 3 0 3 7 ft 7 2 3 1 2 0 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 3 2 1 0 1 2 3 m m Unit ft s m s 0 1 2 3 4 5 6 7 8 ft 7 14 20 2...

Страница 14: ...e view Vertical airflow direction louver Down Horizontal airflow direction louver Center 3 2 1 0 m m Unit ft s m s 0 1 2 3 4 5 6 7 8 ft 7 14 20 27 10 7 3 0 ft 7 2 3 1 2 0 5 10 WALL MOUNTED RIWH18 24AV...

Страница 15: ...rection louver Left Right 3 2 1 0 1 2 3 m m Unit ft s m s 0 1 2 3 4 5 6 7 8 ft 7 14 20 27 10 7 3 0 3 7 10 ft 2 0 5 2 0 5 3 1 3 1 7 2 7 2 Side view Vertical airflow direction louver Up Horizontal airfl...

Страница 16: ...56 CFM 541 MED m3 h 740 l s 206 CFM 435 LOW m3 h 620 l s 172 CFM 365 QUIET m3 h 520 l s 144 CFM 306 Heating Fan speed Airflow HIGH m3 h 920 l s 256 CFM 541 MED m3 h 740 l s 206 CFM 435 LOW m3 h 620 l...

Страница 17: ...659 MED m3 h 900 l s 250 CFM 530 LOW m3 h 740 l s 206 CFM 435 QUIET m3 h 620 l s 172 CFM 365 Heating Fan speed Airflow HIGH m3 h 1 150 l s 319 CFM 677 MED m3 h 900 l s 250 CFM 530 LOW m3 h 740 l s 20...

Страница 18: ...bar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH QUIET Model RIWH24AVFJ Cooling NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC...

Страница 19: ...evel check point 2 ft 7 5 8 in 0 8 m 3 ft 3 3 8 in 1 m Microphone Microphone NOTE Detailed shape of the actual indoor unit might be slightly different from the one illustrated above 15 WALL MOUNTED RI...

Страница 20: ...Current fuse 250 V 3 A Fan motor protection Thermistor protection Activate More than 185 F 85 C Fan motor speed down Reset Less than 185 F 85 C Fan motor speed recover Power IC thermal shutdown protec...

Страница 21: ...ble is 492 ft 150 m The wire connection should be separate from the power cable line Control input Operation Stop or Forced stop The air conditioner can be remotely operated by means of the following...

Страница 22: ...33 ft 10 m Use non polar relays and switches When function setting is Operation Stop mode Operation Stop On Off Input signal Indoor unit When function setting is Forced stop mode Remote controller On...

Страница 23: ...utput Circuit diagram example Locally purchased Indoor unit control PCB Connected unit Example Display Example Relay unit Relay power supply DC 24 V 1 2 Signal V Connector 33 ft 10 m Make the distance...

Страница 24: ...for the initial test in the unit installation i CLOCK ADJUST button Used for adjusting the clock j TIMER MODE button Selects the timer mode off timer on timer program timer and timer reset k SLEEP but...

Страница 25: ...ght oz g 3 85 without batteries NOTE Actual number of buttons might be different from the figure above Holder Unit in mm Front view Side view Bottom view 2 3 8 60 4 1 3 16 30 2 1 8 3 5 1 8 x 1 4 3 5 x...

Страница 26: ...e remote controller custom code Use the following steps to select the custom code of the remote controller Note that the air con ditioner cannot receive a custom code if the air conditioner has not be...

Страница 27: ...een the left and right digits press the MODE but ton 4 Press the TIMER MODE button and START STOP button in the order listed to confirm the settings 5 Press the RESET button to cancel the function set...

Страница 28: ...External input control 7 48 Room temperature sensor switching Aux 8 92 93 Room temperature control for wired remote controller sensor 9 94 Fixed operation mode switching 10 95 Heat insulation conditi...

Страница 29: ...F 3 5 C 09 8 F 4 0 C 10 1 F 0 5 C Less cooling More heating 11 2 F 1 0 C 12 3 F 1 5 C 13 4 F 2 0 C 14 5 F 2 5 C 15 6 F 3 0 C 16 7 F 3 5 C 3 Auto restart Enables or disables automatic restart after a p...

Страница 30: ...ting 46 00 Operation Stop mode 01 Setting prohibited 02 Forced stop mode 7 Room temperature sensor switching Aux To use the temperature sensor on the wired remote controller only change the setting to...

Страница 31: ...ly or cooling only Function number Setting value Setting description Factory setting 94 00 Heat pump 01 Heating only 02 Cooling only 10 Heat insulation condition building insulation Heat insulation co...

Страница 32: ...play to the air conditioner custom code 4 Press the MODE button again to return to the clock indicator The custom code will be changed NOTES If no button is pressed within 30 seconds after the custom...

Страница 33: ...1 Drain hose insulation 1 Installation manual 1 Cloth tape 1 Wall hook bracket 1 Tapping screw large M4 25 mm 8 Remote controller 1 Tapping screw small M3 12 mm 2 Battery 2 Air cleaning filter 2 Remot...

Страница 34: ...by detecting the temperature accurately with built in thermo sensor Wire type Polar 3 wire Simple remote controller RXRSNUM Compact remote controller concentrates on the basic functions such as Start...

Страница 35: ...Part 2 OUTDOOR UNIT SINGLE TYPE ROSH18AXFWJ ROSH24AXFWJ...

Страница 36: ...900 330 Gross in 39 3 8 41 5 16 17 1 2 mm 1 000 1 050 445 Weight Net lb kg 135 61 Gross 152 69 Connection pipe Size Liquid in mm 3 8 9 52 Gas 5 8 15 88 Method Flare Pre charge length ft m 66 20 Max l...

Страница 37: ...4AXFWJ Unit in mm Top view Front view Side view Bottom view 3 77 35 3 8 900 32 3 4 830 17 3 8 440 7 8 21 15 3 4 400 13 330 7 3 4 196 5 3 4 147 6 3 4 170 14 5 8 370 25 5 8 650 Airflow 1 1 4 31 1 2 12 3...

Страница 38: ...4 100 or more 10 250 or more 12 300 or more 4 100 or more When there are obstacles at the front only When there are obstacles at the front and rear 24 600 or more 24 600 or more 4 100 or more When th...

Страница 39: ...50 or more or more 60 1 500 or more 10 250 or more When there are obstacles at the front and rear 20 500 or more 60 1 500 or more 10 250 or more When there is an obstruction in the upper space Unit in...

Страница 40: ...to obtain better opera tion efficiency CAUTION Do not install the outdoor unit in two stage where the drain water could freeze Otherwise the drainage from the upper unit may form ice and cause a malf...

Страница 41: ...J and ROSH24AXFWJ 3 way valve small 3 way valve large Muffler Pressure switch 4 way valve Strainer Expansion valve Strainer Heat exchanger INDOOR Heat exchanger OUTDOOR Sub accumulator Compressor Cool...

Страница 42: ...5 Wiring diagrams 5 1 Model ROSH18AXFWJ 38 OUTDOOR UNIT ROSH18 24AXFWJ...

Страница 43: ...5 2 Model ROSH24AXFWJ 39 OUTDOOR UNIT ROSH18 24AXFWJ...

Страница 44: ...963 0 0 0 998 1 000 1 000 0 976 0 979 0 976 0 971 Indoor unit is lower than outdoor unit 2 5 16 0 998 1 000 1 000 0 976 0 979 0 976 0 971 7 5 24 1 000 1 000 0 976 0 979 0 976 0 971 10 32 1 000 0 976...

Страница 45: ...WJ Refrigerant type R410A Refrigerant amount lb oz 4 lb 10 1 oz g 2 100 Refrigerant charge Total pipe length ft 66 or less 98 131 164 Max 0 43 oz ft 40 g m m 20 or less 30 40 50 Max Additional charge...

Страница 46: ...el ROSH18AXFWJ Cooling m3 h 2 530 l s 703 CFM 1 489 Heating m3 h 2 530 l s 703 CFM 1 489 8 2 Model ROSH24AXFWJ Cooling m3 h 3 400 l s 944 CFM 2 001 Heating m3 h 3 600 l s 1 000 CFM 2 119 42 OUTDOOR UN...

Страница 47: ...0 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Model ROSH24AXFWJ Cooling Octave band sound pressure level dB 0 dB 0 0002 bar Octave ban...

Страница 48: ...heck point 39 3 8 in 1 m Microphone Microphone Rear Airflow Rear view Side view NOTE Detailed shape of the actual outdoor unit might be slightly different from the one illustrat ed above 44 OUTDOOR UN...

Страница 49: ...ength ft m 167 51 1 Minimum Circuit Ampacity Calculation based on UL1995 2 Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 As the regulations of wire size and circu...

Страница 50: ...t 248 27 18 F 120 15 10 C Fan motor restart Compressor protection Terminal protection program Compressor temp Activate 226 F 108 C Compressor stop Reset 176 F 80 C Compressor restart Thermal protectio...

Страница 51: ...Part name Exterior Q ty Part name Exterior Q ty Installation manual 1 Adapter 12 7 1 2 15 88 5 8 mm in Only for 18 model 1 Drain pipe 1 Adapter 6 35 1 4 9 52 3 8 mm in 1 Drain cap 5 47 OUTDOOR UNIT R...