8. TROUBLESHOOTING
If these solutions, below, do not work, contact your dealer.
Do not attempt to repair the heater yourself.
Failure
Reason
Solution
Swimming
Pool Heat
Pump Does
Not Run
Main power off
Wait for the power to be
restored
Power switch
is off
Turn on switch
Fuse burnt
Replace fuse
Circuit breaker
tripped
Turn circuit breaker back on
Heat Pump
Runs but
Does Not
Heat
Air inlet blocked
Remove obstructions
Air outlet
blocked
Remove obstructions
3-minute
protection
Please wait more than 3
minutes for warming to start
Temp set too
low
Set temperature setting
Table G. Common Faults
Fault Codes
Failure Code
Failure Description
E1
High pressure protection
E2
Low pressure protection
E3
Low water pressure protection
E4
Single phase unit: loose wire terminal at
PROT2 on the PC board
Three phase unit: 3 phase sequence
protection
P1
Pool water temp sensor failure
P2
Exhaust temp sensor failure (cooling coil
temp for heat and cooling models only)
P3
Heating coil pipe temp sensor failure
P4
Gas return temp sensor failure
P5
Air temp sensor failure
E6
Compressor exhaust overload protection
212°F (100°C) (Heating models only)
P7
When air temp <32°F (0°C), the unit is in
auto-stop protection mode, or anti-freeze
mode (not a failure)
HEAT flashing Defrosting (not a failure)
Table H. Fault Codes - On/Off Models Only
No.
Display
Non-Failure Description
1
E3
No water protection
2
E5
Power supply excesses operation range
3
E6
Excessive temp difference between inlet
and outlet water
(insufficient water flow protection)
4
Eb
Ambient temperature too high or too low
protection
5
Ed
Anti-freezing reminder
No.
Display
Failure Description
1
E1
High pressure protection
2
E2
Low pressure protection
3
E4
3 phase sequence protection
(three phase only)
4
E7
Water outlet temp too high or too low
protection
5
E8
High exhaust temp protection
6
EA
Evaporator overheat protection
(only at cooling mode)
7
P0
Controller communication failure
8
P1
Water inlet temp sensor failure
9
P2
Water outlet temp sensor failure
10
P3
Gas exhaust temp sensor failure
11
P4
Evaporator coil pipe temp sensor failure
12
P5
Gas return temp sensor failure
13
P6
Cooling coil pipe temp sensor failure
14
P7
Ambient temp sensor failure
15
P8
Cooling plate sensor failure
16
P9
Current sensor failure
17
PA
Restart memory failure
18
F1
Compressor drive module failure
19
F2
PFC module failure
20
F3
Compressor start failure
21
F4
Compressor running failure
22
F5
Inverter board over current protection
23
F6
Inverter board overheat protection
24
F7
Current protection
25
F8
Cooling plate overheat protection
26
F9
Fan motor failure
27
Fb
Power filter plate no-power protection
28
FA
PFC module over current protection
Table I. Fault Codes - Inverter Models Only
Содержание Raypak CROSSWIND-30-I
Страница 14: ...14 5 WIRING DIAGRAMS Crosswind 30 I 50 I Touch Controller...
Страница 15: ...15 Crosswind 40 I Touch Controller...
Страница 16: ...16 Crosswind 65 I Touch Controller...
Страница 17: ...17 LED Controller Automation Controller Crosswind 40 O...
Страница 18: ...18 LED Controller Automation Controller Crosswind 50 O...
Страница 19: ...19 LED Controller Automation Controller Crosswind 65 O...
Страница 33: ...33 NOTES...
Страница 34: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com www raypak com...
Страница 67: ...33 NOTES...
Страница 68: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com www raypak com...