CONNECTIONS – ELECTRICAL
45
BOOSTER CONTROL
The isolating switch installed in the electrical meter box for the solar storage tank should be left switched on.
Leaving the isolating switch switched on will also provide a sufficient period of time each day for the booster
heating unit to operate, if required, to satisfy the requirements of AS 3498.
Timer Control Switch
A suitably rated timer control switch can be installed and will help maximise energy savings with an electrically
boosted solar water heater connected to a
continuous, time of use
or extended Off-Peak (overnight and
day)
electricity supply.
If used with an extended Off-Peak (overnight and day) electricity supply, the timer switch should:
be operated by a continuous power supply on its own circuit from the switchboard with the booster heating
unit operated by the Off-Peak power supply. A double pole isolating switch is required to be installed at
the switchboard to simultaneously isolate both circuits.
or
be of a type which has an internal rechargeable battery to keep time when the power supply is not available
to the timer.
Refer to
on page 8 for information on programming the timer.
WIRING DIAGRAM
– TIMER CONTROL SWITCH
CONTINUOUS
POWER SUPPLY
Switchboard
EXTENDED OFF-PEAK
POWER SUPPLY
Switchboard
Timer
Terminal Block
TIMER WITHOUT CONTACTOR
Timer
Terminal Block
TIMER WITH CONTACTOR (if required)
EXTENDED OFF-PEAK
POWER SUPPLY
(timer with rechargeable battery)
Switchboard
TIMER WIRING DIAGRAMS
ELECTRIC BOOSTED DIRECT SOLAR WATER HEATER